8.14.3
Connection information
Characteristic
Description
Cable length
max 15 m.
Current capability
Conform application
Capacitance
max 100 pF/m.
Tab. 8-15:
Motor cable characteristics
The motors are connected according to
fig. 8-16 "NY4120 motor connection
tab. 8-16 "Motor connections" on page 81
.
2.2uF
Node
DP_PWR
DP_GND
Current
measurement
Current
measurement
Shortcircuit
detection
[See Note 5]
[See Note 4]
[See Note 3]
Drive
Power
Supply
Node
HB1+ HB3+
HB1- HB3-
HB2+ HB4+
HB2- HB4-
M0
M1
[See Note 3]
filter
filter
DR_PWR
DR_GND
Fig. 8-16:
NY4120 motor connection circuit
Notes
1. Follow this cabling instruction:
Shielded cable is recommended, but not mandatory.
If shielded cable is used, the shielding on the NYCe 4000 side of the
cable must be connected to Shield (house connector).
Connect the other side to a convenient metal part or leave it open.
2. Connect the DR_GND of the drive power to the housing and/or safety
earth (if this is not already the case).
3. Connect the NYCe 4000, a power supply or other equipment on a metal
frame or mounting base and make sure there is a galvanic contact.
4. A fuse must be installed between the +V of the drive power supply and
DP_PWR on the node. The fuse is mandatory by safety regulations and
must be UL recognized. See NYCe 4000 Standard Housings and
Accessories manual for detailed information about fuses.
5. Connect an external capacitor close to the drive module (see
16.1 "Drive Power Filtering for NY412x/NY4140" on page 213
), in
order to avoid ripple currents.
80/233
NY4120 and NY4120/10: PWM Drive Module
NYCe 4000 Multi-axis motion control system Hardware Sys‐
tem Manual
Bosch Rexroth AG R911337671_Edition 18