High side switching (HSS)
Inp_Common
Inp_
+24 Volt
0 Volt
Node
Application
PNP
High side switching (HSS)
Inp_Common
Inp_
+24 Volt
0 Volt
Node
Application
Low side switching (LSS)
Inp_Common
Inp_
Node
Application
0 Volt
+24 Volt
Low side switching (LSS)
Inp_Common
Inp_
Node
Application
0 Volt
+24 Volt
NPN
Fig. 7-5:
HSS and LSS
7.7
ETH1, ETH2, ETH3 connection information
Characteristic
Description
Cable length
max 100 m.
Type of cable
Crossed or straight
transmission speed 100 Mbps (100BASE-TX)
Cat-5 STP
transmission speed 1 Gbps (1000BASE-T)
Cat-5e STP or better
Default IP address (IPv4)
192.168.41.14
Default subnet mask
255.255.255.0
Default gateway
0.0.0.0
Tab. 7-8:
NY4114 connection characteristics
7.8
USB connection information
On the front of the MCU module is one microUSB "On-The-Go" USB 2.0 port.
This USB port can be used to connect a memory stick to the MCU. You can
copy data from the memory stick and write the data to the flash memory of
the MCU, or read data from the flash memory of the MCU and store the data
on the memory stick.
Damage to the MCU may occur if external
power is connected to the USB connector.
WARNING
●
Do not connect an external (USB) power supply to the USB port of the
MCU module.
NYCe 4000 Multi-axis motion control system Hardware Sys‐
tem Manual
51/233
NY4114: Ethernet MCU Module
R911337671_Edition 18 Bosch Rexroth AG