Commissioning • Connection examples
180
Automation PC 810 with GM45 CPU board user's manual V1.28
5.2 One Automation Panel 900 via onboard DVI
An Automation Panel 900 with max. SXGA resolution is connected to the integrated DVI interface (onboard). As an
alternative, an office TFT with DVI interface or an analog monitor (using adapter with model no. 5AC900.1000-00)
can also be used. A separate cable is used for touch screen and USB. If USB devices are to be operated on the
Automation Panel 900, the maximum distance is 5 meters. USB devices can only be connected directly to the
Automation Panel (without a hub).
Automation PC 810
DVI cables
RS232 cables
USB cables
Segment length 5 m (with USB)
Max. 10 m (without USB)
Link: 5DLDVI.1000-01
USB up to
5 m OK
Monitor / Panel
Connection
Figure 84: One Automation Panel 900 via onboard DVI (sample photo)
5.2.1 Basic system requirements
The following table shows the possible combinations of APC810 system unit and CPU board to implement the
configuration shown in the figure above. If a combination results in a limitation of the maximum resolution, this is
also indicated (e.g. when connecting a non-B&R Automation Panel 900 device).
with system unit
CPU board
5PC810.SX01-00
5PC810.SX02-00
5PC810.SX03-00
5PC810.SX05-00
Limitation
Resolution
5PC800.BM45-00
✓
✓
✓
✓
Max. SXGA
5PC800.BM45-01
✓
✓
✓
✓
Max. SXGA
Table 133: Possible combinations of system unit and CPU board
5.2.2 Link modules
Information:
A corresponding link module must be selected for every device used.
Model number
Description
Note
5DLDVI.1000-01
Automation Panel Link DVI receiver
connections for DVI-D, RS232 and USB 2.0 (Type B); 24 VDC (screw clamp 0TB103.9 or cage clamp
0TB103.91 sold separately).
For Automation Panel 900
Table 134: Link modules
5.2.3 Cables
Select one Automation Panel 900 cable each from the 3 required types.
Model number
Description
Length
5CADVI.0018-00
DVI-D cable, 1.8 m.
1.8 m ±50 mm
5CADVI.0050-00
DVI-D cable, 5 m.
5 m ±80 mm
5CADVI.0100-00
DVI-D cable, 10 m.
10 m ±100 mm
9A0014.02
RS232 extension cable for remote operation of a display unit with touch screen, 1.8 m.
1.8 m ±50 mm
9A0014.05
RS232 extension cable for remote operation of a display unit with touch screen, 5 m.
5 m ±80 mm
9A0014.10
RS232 extension cable for remote operation of a display unit with touch screen, 10 m.
10 m ±100 mm
5CAUSB.0018-00
USB 2.0 connection cable type A - type B, 1.8 m.
1.8 m ±30 mm
5CAUSB.0050-00
USB 2.0 connection cable type A - type B, 5 m.
5 m ±50 mm
Table 135: Cables for DVI configurations