Technical data • Individual components
142
Automation PC 810 with GM45 CPU board user's manual V1.28
Product ID
5ACPCI.RAIC-06
Recommendations
Specified standard
CE (CE)
Yes
UL 508 (cULus)
LISTED 14F2 BR
Table 88: 5ACPCI.RAIC-06 - Technical data
1)
Technical data for a hard disk.
2)
With 8760 POH (power on hours) per year and 25°C surface temperature.
3)
Temperature values for 305 meter altitude. The temperature specification must be reduced linearly by 1 °C every 305 meters. The temperature increase
and decrease can be a maximum of 20 °C per hour.
4)
Standard operation means 333 POH (power-on hours) per month.
5)
24-hour operation means 732 POH (power-on hours) per month.
6)
Humidity gradient: Maximum 20% per hour.
7)
Operation in areas prone to vibration and shock can affect performance negatively (reduction of transfer rate).
8)
Mounted on PCI insert.
3.6.16.4 Temperature humidity diagram
Temperature [°C]
R
el
at
iv
e
hu
m
id
ity
[%
R
H
] (
no
n-
co
nd
en
si
ng
)
Operation
Storage
Transport
Figure 58: 5ACPCI.RAIC-06 - Temperature humidity diagram
3.6.16.5 Driver support
Special drivers are necessary for operating the PCI SATA RAID controller. Drivers for supported and approved
operating systems are available in the Downloads section of the B&R website (
The .NET-based SATA Raid™ serial ATA RAID management software can also be found on the B&R homepage.
Information:
Required drivers can only be downloaded from the B&R website, not from manufacturer websites.
3.6.16.6 Configuration
Configuring a SATA RAID network: see Chapter 3 "Commissioning", section 7 "Configuration of a SATA RAID
3.6.16.7 Exchanging a HDD
A hard drive can be easily exchanged in the event of an error when using the RAID1 (mirroring) configuration without
having to re-install the system. Here, the 500 GB 5MMHDD.0500-00 SATA HDD is available as a replacement
hard disk.
Instructions for exchanging see "Exchanging a PCI SATA RAID hard disk in a RAID 1 system" on page 400.