4-12 Input / Output
MN1901
4.3.5 Relay output / digital output - X3
Location
Connector X3, pins 4 (+) & 5 (-)
Name
General purpose relay
Mint keyword
RELAY
/
OUTX.3
Description
Relay switch contacts controlled by Mint, rated at 1A,
30VDC.
Update interval: Immediate
The factory preset assignment for the relay is as the global error output signal
(see the Mint keyword
GLOBALERROROUTPUT
). When an error occurs the relay
is de-energized and the contacts open. When the error is cleared, the relay is
re-energized and the contacts close. The relay can be also be controlled
directly by the Mint keyword
RELAY
. When the relay is energized (
RELAY=_on
)
the contacts close. When the relay is de-energized (
RELAY=_off
) the contacts
open. The relay output may also be considered as a digital output, so can be
controlled directly using the Mint keyword
OUTX
(for example
OUTX.3=1
).
Internal relay
MintDrive
II
Control
circuitry
Relay +
Relay -
4
5
‘X3’
Figure 34 - Relay contact outputs
Note:
The internal relay has a limited lifetime and is not intended for continuous cyclical
operation. If relay operations are required more frequently than 4 - 5 times per
hour, it is recommended to use one of the digital outputs to control a replaceable
external relay.
4
5
Summary of Contents for MDH1A05TB-RC23
Page 1: ...MintDriveII Servo Position Control SERVO DRIVE Installation Manual 01 07 MN1901...
Page 2: ......
Page 14: ...www baldormotion com 2 4 Introduction MN1901...
Page 94: ...www baldormotion com 6 10 Preset Moves PLC Task MN1901...
Page 122: ...www baldormotion com A 10 Accessories MN1901...
Page 130: ...www baldormotion com B 8 Control System MN1901...
Page 158: ...www baldormotion com D 6 CE Guidelines MN1901...
Page 164: ...www baldormotion com Comments MN1901 Thank you for taking the time to help us...
Page 165: ......