Basic Installation 3-13
MN1901
3.4.6 Wire sizes and protection device ratings
Table 2 describes the wire size to be used for power connections and the ratings of the
protection devices.
Incoming Power
C t l
N
b
Nominal
Input
Continuous
Output
D-Type
Input
Time
Delay
Minimum
Catalog Number
Input
Voltage
Output
Amps
yp
Input
Breaker
Delay
Input
Minimum
Wire Gauge
Voltage
Amps
(RMS)
Breaker
(A)
Input
Fuse
(A)
AWG
mm
2
MDH1A02
xx-xxxx
115V (1
Φ
)
2.5A
6
6
14
2.0
MDH2A02
xx-xxxx
230V (1
Φ
)
2.5A
6
6
14
2.0
MDH1A05
xx-xxxx
115V (1
Φ
)
5A
10
10
14
2.0
MDH2A05
xx-xxxx
230V (1
Φ
)
5A
10
10
14
2.0
MDH1A07
xx-xxxx
115V (1
Φ
)
7.5A
16
16
14
2.0
MDH2A07
xx-xxxx
230V (1
Φ
)
7.5A
16
16
14
2.0
MDH4A02
xx-xxxx
230-460V
(3
Φ
)
2.5A
6
6
14
2.0
MDH4A05
xx-xxxx
230-460V
(3
Φ
)
5A
10
10
14
2.0
MDH4A07
xx-xxxx
230-460V
(3
Φ
)
7.5A
16
16
14
2.0
MDH2A15
xx-xxxx
230V (3
Φ
)
15A
32
32
12
3.3
MDH4A15
xx-xxxx
230-460V
(3
Φ
)
15A
32
32
12
3.3
MDH4A20
xx-xxxx
230-460V
(3
Φ
)
20A
40
40
10
5.3
MDH4A27
xx-xxxx
230-460V
(3
Φ
)
27.5A
60
60
10
5.3
Table 2 - Protection device and wire ratings
Note:
All wire sizes are based on 75°C (167°F) copper wire. Higher temperature smaller
gauge wire may be used per National Electric Code (NEC) and local codes.
Recommended fuses/breakers are based on 25°C (77°F) ambient, maximum
continuous control output current and no harmonic current. Earth/ground wires
must be the same gauge, or larger, than the Line and Neutral wires.
Summary of Contents for MDH1A05TB-RC23
Page 1: ...MintDriveII Servo Position Control SERVO DRIVE Installation Manual 01 07 MN1901...
Page 2: ......
Page 14: ...www baldormotion com 2 4 Introduction MN1901...
Page 94: ...www baldormotion com 6 10 Preset Moves PLC Task MN1901...
Page 122: ...www baldormotion com A 10 Accessories MN1901...
Page 130: ...www baldormotion com B 8 Control System MN1901...
Page 158: ...www baldormotion com D 6 CE Guidelines MN1901...
Page 164: ...www baldormotion com Comments MN1901 Thank you for taking the time to help us...
Page 165: ......