www.baldormotion.com
4-20 Input / Output
MN1901
4.4.6 Connecting Baldor HMI Operator Panels
Baldor HMI Operator Panels use a 15-pin male D-type connector (marked PLC PORT), but
the MintDrive
II
connector X6 is a 9-pin male D-type connector. If you do not require hardware
handshaking then use the connections shown in Figure 43:
7 RTS
8 CTS
3 TXD
2 RXD
5 GND
1
RXD 2
TXD 3
GND 5
Baldor HMI
PLC PORT
MintDrive
II
X6
Twisted pair
Figure 43 - Cable wiring if hardware handshaking is
not
required
If hardware handshaking is required then use the connections shown in Figure 44:
7 RTS
8 CTS
3 TXD
2 RXD
5 GND
1
RXD 2
TXD 3
GND 5
Baldor HMI
PLC PORT
MintDrive
II
X6
CTS 11
RTS 10
Twisted pair
Figure 44 - Cable wiring if hardware handshaking
is
required