www.baldormotion.com
4-2 Input / Output
MN1901
4.2.1 Analog input - X3 (demand)
Location
Connector X3, pins 1-3
(Mating connector:
Phoenix MINI-COMBICON MC 1.5/20-ST-3,5)
Name
AIN0
Mint keyword
ADC.0
Description
Single ended or differential input.
Common mode voltage range: ±10VDC.
Resolution: 14-bit with sign (accuracy ±1.2mV)
Common mode rejection: 40dB
Input impedance: >5k
Ω
Sampling interval:
500
μ
s - Software (Mint programs)
125
μ
s - High speed demand
reference signal
Analog input X3 can be connected as either a differential or a single ended input as shown in
Figure 25.
10k
LF412
AGND
Mint
ADC.0
MintDrive
II
10k
10k
10k
-15V
+15V
-15V
+15V
20k
-
+
20k
Low pass filter &
level correction
(inverts signal)
AIN0+
AIN0-
2
1
‘X3’
Figure 24 - AIN0 analog input circuit
1
2
3
Summary of Contents for MDH1A05TB-RC23
Page 1: ...MintDriveII Servo Position Control SERVO DRIVE Installation Manual 01 07 MN1901...
Page 2: ......
Page 14: ...www baldormotion com 2 4 Introduction MN1901...
Page 94: ...www baldormotion com 6 10 Preset Moves PLC Task MN1901...
Page 122: ...www baldormotion com A 10 Accessories MN1901...
Page 130: ...www baldormotion com B 8 Control System MN1901...
Page 158: ...www baldormotion com D 6 CE Guidelines MN1901...
Page 164: ...www baldormotion com Comments MN1901 Thank you for taking the time to help us...
Page 165: ......