–36–
009 Input Type
Enter the input device type as follows:
6=serial number polling loop device (SL type); 7 =DIP
switch type (left loop) polling loop device (DP type);
8=right loop of DIP switch type device (PS type).
UL
Right loops refer to the use of the right (or secondary) loop on a 4190WH zone
expander module and/or 4278 PIR. This loop allows only standard N.C. non-
supervised devices to be monitored by the polling loop. Right loops CANNOT be
used in UL installations).
009 LOOP NUMBER
If this is a previously "learned" sensor, the loop
number for this zone will appear. Press
✴
to
continue
OR
009 LEARN S/N ?
1=YES 0=NO
If type 6 was entered, and the sensor's serial
number has not been "learned," the serial number
can be learned now by entering 1 , or it can be
learned later by using the SERIAL NUMBER LEARN
menu. Enter 0 if serial number will be learned later.
The summary screen will then appear (see summary
screen description above).
009 INPUT S/N :L
A000-0000:1
If learning the serial number now (entering 1 at the
last prompt), this prompt appears. Fault the sensor
two times. The keypad will beep twice after the first
fault and three times upon receiving a matching fault
signal. When the serial number has been
successfully learned, its number appears in the
display. A typical display is shown.
Alternatively, the 7-digit serial number can be
entered manually through the keypad, if printed on
the unit itself.
009 PROG AS SL:1
A001-3078:1
Press
✴
to continue. The summary screen will
then appear as it did when first entering the zone
number to be programmed (see summary screen
description above).
Press
✴
to display the "ENTER ZN NO?" prompt
for programming the next zone.
After all zones have been programmed, enter 000 at
this prompt and press
✴
. This will exit out of
Menumode programming and return to normal (data
field) programming mode.
Press *99 to exit program mode.
Check-Out Procedure For Polling Loop Zones
After installation of all polling loop zones is complete,
each partition of the
security system should be checked as follows:
1. Be sure that all devices and sensors connected to the polling loop are not in a
faulted state. Doors and windows with contacts should be closed, PIRs
should be covered (use a cloth to mask them temporarily if necessary).
2. With all hard-wired and polling loop zones intact, the Alpha keypads
connected to the system should display:
DI S ARME D
RE ADY TO ARM.
www.PDF-Zoo.com
firealarmresources.com
Summary of Contents for VISTA-100
Page 197: ... 187 Insert DIP Switch Table Board A www PDF Zoo com firealarmresources com ...
Page 198: ... 188 Insert DIP Switch Table Board B www PDF Zoo com firealarmresources com ...
Page 199: ... 189 Insert DIP Switch Table Board C www PDF Zoo com firealarmresources com ...
Page 206: ... 196 NOTES www PDF Zoo com firealarmresources com ...