– 102 –
*35
DOWNLOAD PHONE NO.
| | | | | | | | | | | | | | | | |
This field is applicable only if downloading will be utilized.
Enter the downloading phone number, up to 17 digits, 0-9; enter #11 for
*, #12 for #, and #13 for a 2 sec. pause. Do not fill unused spaces.
*36
DOWNLOAD ID NO. | | | | | | | |
Enter eight digits, 00-09; A-F (10-15). Only applicable if downloading will
be utilized. Make entries as 2-digit numbers as follows:
00=0
02=2
04=4
06=6
08=8
10=A
12=C
14=E
01=1
03=3
05=5
07=7
09=9
11=B
13=D
15=F
*37
DOWNLOAD COMMAND ENABLES
0
Dialer
System
Not
Remote
Remote
Remote
Upload
Download
Shutdwn Shutdwn
Used
Bypass
Disarm
Arm
Program
Program
Each of the various remote functions can either be enabled or disabled
through VLink downloading software. Disabling a function means that
you will not be able to perform that function from the VLink. Enter 1 to
enable a function, and 0 to disable a function. See field 1*53 to disable
the download callback option. For Commercial Fire and UL Commercial
Burglary installations, all entries must be 0.
*38
PREVENT ZONE XXX BYPASS (partition-specific)
[00] | |
Entering a zone number (001-087) prevents that zone from being
bypassed by the user. Enter 00 if this feature is not desired (all zones
can be bypassed).
*39
ENABLE OPEN/CLOSE REPORT FOR INSTALLER CODE
(partition-specific)
[0]
Enter 1
if open/close reporting for the installer is desired.
Otherwise enter 0.
*40
OPEN/CLOSE REPORTING FOR KEYSWITCH
[0]
Enter 1 to enable open/close reporting for the keyswitch.
Enter 0 if reporting is not desired.
*41
NORMALLY CLOSED OR EOLR (ZONES 3-8)
[1]
Enter 0 if end-of-line resistors are to be used.
Enter 1 if end-of-line resistors are not to be used, in which case only
normally closed devices must be used.
Must be 0 for Commercial Fire and UL installations.
*42
DIAL TONE PAUSE
[0]
This field sets the time the system will wait for dial tone before dialing.
Applies if true dial tone is not selected in field *43.
Enter the desired wait time for dial tone detection as follows: Enter
single digit, 0 = 5 seconds; 1 = 11 seconds; or 2 = 30 seconds. Must be
0 for Commercial Fire and UL installations.
www.PDF-Zoo.com
firealarmresources.com
Summary of Contents for VISTA-100
Page 197: ... 187 Insert DIP Switch Table Board A www PDF Zoo com firealarmresources com ...
Page 198: ... 188 Insert DIP Switch Table Board B www PDF Zoo com firealarmresources com ...
Page 199: ... 189 Insert DIP Switch Table Board C www PDF Zoo com firealarmresources com ...
Page 206: ... 196 NOTES www PDF Zoo com firealarmresources com ...