![ADEMCO VISTA-100 Installation Instructions Manual Download Page 189](http://html1.mh-extra.com/html/ademco/vista-100/vista-100_installation-instructions-manual_2850251189.webp)
– 179 –
Burglary Walk Test (code + TEST [5])
This test causes the system to sound keypad beeps in response to faults on
burglary and non-fire related 24 hour zones for the purpose of allowing
proper zone operation to be checked without triggering alarms. Note that
the system will not trigger alarms for burglary and non-fire related 24 hour
zones but will trigger fire alarms while this test is active. This test can only
be activated by the installer, a master user or manager user by entering the
corresponding security code and pressing TEST while the burglary portion of
the system is disarmed. UL requires that this test be conducted on a weekly
basis.
When this test is first activated, the system will sound burglary bells (or any
bell having a non-zero response type in each bell's supervisory zone) for 3
seconds. The system will send a start of walk test message to the central
station. The keypads will display “Burg Walk Test in Progress” and will
sound a single beep every 15 seconds while the test remains active.
Open and close each protected door and window in turn. Each action should
produce 3 beeps from the keypad. Walk in front of any motion detectors.
Listen for three beeps when the detector senses movement. The keypad will
display the zone number and alpha descriptor while a door or window
remains open or while a detector remains activated. The system
automatically issues a zone 8 glass break detector power reset about 10
seconds after it finds a fault on this zone, to allow faulted detectors to be
reset.
To end this test, enter any security code and press OFF. An end-of-walk test
message will be sent to the central station.
Armed Burglary System Test
1. Alarm messages will be sent to the central station during the following
tests. Notify the central station that a test will be in progress.
2. A display of "COMM. FAILURE" indicates a failure to communicate (no
Kissoff by the receiver at the central station after the maximum number
of transmission attempts is tried). If this occurs, verify that the phone
line is connected, the correct report format is programmed, etc.
1.
Arm the system and fault one or more zones. Silence alarm sounder(s)
each time by entering the code and pressing OFF. Check that Entry/Exit
delay zones provide the assigned delay times.
2.
Check the keypad-initiated alarms, if programmed, by pressing the
Panic keys (* and #, 1 and *, and/or 3 and #). If the system has been
programmed for audible emergency, the keypad will emit a loud, steady
alarm sound. The word ALARM and a descriptor "999" will be displayed
for * and #. (if 1 and * are pressed, a "995" will be displayed; if 3 and #
are pressed, a "996" will be displayed). Silence the alarm by entering the
security code and pressing OFF. If the system has been programmed for
silent panic, there will be no audible alarms or displays. A report will be
sent to the central station, however.
3.
Notify the central station that all tests are finished and verify results
with them.
www.PDF-Zoo.com
firealarmresources.com
Summary of Contents for VISTA-100
Page 197: ... 187 Insert DIP Switch Table Board A www PDF Zoo com firealarmresources com ...
Page 198: ... 188 Insert DIP Switch Table Board B www PDF Zoo com firealarmresources com ...
Page 199: ... 189 Insert DIP Switch Table Board C www PDF Zoo com firealarmresources com ...
Page 206: ... 196 NOTES www PDF Zoo com firealarmresources com ...