– 76 –
Event Log Printer Connections
The VISTA-100's event log can be printed on a local serial printer. If used,
program field 3*19 must be set to "1."
This setting overrides the functions selected for INPUT 1 and OUT 2 made in
field 3*20.
Connect a UL EDP Listed serial printer to the J2 connector using an Ademco
4100SM Interface module. Refer to
Section 16:
EVENT LOG OPTIONS of this
manual for wiring connections, printer configuration, and a description of the
keypad commands which initiate event log printing.
If earth ground fault sensing is enabled:
1.
You may get an earth ground fault indication when the 4100SM module
is clipped directly onto a sidewall of the VISTA-100 cabinet. If this occurs,
use an insulator to insulate the 4100SM's clip-on bracket from the
VISTA-100 cabinet side wall. Later production versions of the 4100SM
have the clip-on bracket isolated from the circuit ground (terminal 7) and
will not have this problem.
2.
You may also get an earth ground fault indication if you use a printer (or
PC) which has a 3-prong, grounded power cord. If this occurs, first verify
that pin 1 (chassis ground) is isolated from pin 7 (signal ground) on the
4100SM's RS232 connector (early production versions of the 4100SM
have an unmarked, 3/8' long, bare wire jumper lying near the pin 1 side
of the RS232 connector which must be cut to isolate these pins). Then
verify that these pins are isolated on your printer's RS232 connector.
Follow the instructions provided with your printer to isolate these pins if
required.
Direct Wire Downloading
The VISTA-100 can be downloaded without using a modem or telephone line, but
by using a 4100SM Serial Module (and VLINK Downloading Software) . This
method of downloading is referred to as DIRECT WIRE downloading. Connect a
PC which runs the downloading software to the 4100SM module as specified in
the module's instructions. Connect the 4100SM to the panel's J2 header. Refer
to
Section 25: DOWNLOADING PRIMER
for wiring connections.
Direct wire downloading can be initiated by following the procedures described in
the VLINK manual.
www.PDF-Zoo.com
firealarmresources.com
Summary of Contents for VISTA-100
Page 197: ... 187 Insert DIP Switch Table Board A www PDF Zoo com firealarmresources com ...
Page 198: ... 188 Insert DIP Switch Table Board B www PDF Zoo com firealarmresources com ...
Page 199: ... 189 Insert DIP Switch Table Board C www PDF Zoo com firealarmresources com ...
Page 206: ... 196 NOTES www PDF Zoo com firealarmresources com ...