– 95 –
Section 19: ZONE TYPE DEFINITIONS
This section provides the following information:
•
Zone number designations
•
Zone Type Definitions
The VISTA-100 supports up to 86 zones of hard-wire, polling loop and/or wireless
protection, distributed among up to 8 partitions. The following table lists the zone
numbers and the types of sensors that can be used with each in this system:
Zone
Sensors
1 & 2
2-wire smoke detectors (if used)
7
keyswitch (if used)
8
latching type glass break detectors (if used)
1-8
traditional hard-wired zones
1-63
5700 series wireless devices
1-87
5800 series wireless devices
10-87
polling loop devices
995
*/1 panic
996
#/3 panic
999
*/# panic
Each zone must be assigned a zone type, which defines the way in which the
system responds to faults in that zone. In addition, there are three keypad
activated zones (PANIC keys, see note) for each partition, a polling loop
supervision zone, and four RF supervisory zones, two for each RF Receiver
installed. Zone types are defined below.
Type 00: Zone Not Used
Program a zone with this zone type if the zone is not
used.
Type 01: Entry/Exit #1 Burglary.
This zone type provides entry delay whenever the
zone is faulted if the control is armed in the Away or
Stay modes. When the panel is armed in the Instant or
Maximum modes, no entry delay is provided. Exit delay
begins whenever the control is armed, regardless of
the arming mode selected. These delays are
programmable. This zone type is usually assigned to
sensors or contacts on doors through which primary
entry and exit will take place.
Type 02: Entry/Exit #2 Burglary.
This zone type provides a secondary entry delay
whenever the zone is faulted if the panel is armed in
the Away and Stay modes. When the panel is armed in
the Instant or Maximum modes, no entry delay is
provided. Secondary exit delay begins whenever the
control is armed, regardless of the arming mode
selected. These delays are programmable. This zone
type is usually assigned to sensors or contacts on
doors through which more time is needed to get to and
from the keypad. Delay times for this zone type must
be greater than Zone Type 01. (Ex.: a garage, loading
dock, or basement door)
Type 03: Perimeter Burglary.
This zone type gives an instant alarm if the zone is
faulted when the panel is armed in the Away, Stay,
Instant or Maximum modes. This zone type is usually
assigned to all sensors or contacts on exterior doors
and windows.
Type 04: Interior, Follower.
This zone type gives a delayed alarm (using the
programmed Entry /Exit time) if the Entry/Exit zone is
faulted first. Otherwise this zone type gives an instant
alarm. This zone type is active when the panel is
armed in the Away or Maximum modes. Maximum
mode eliminates the entry delay. This zone type is
bypassed automatically when the panel is armed in
the Stay or Instant modes. This zone type is usually
assigned to a zone covering an area such as a foyer,
lobby, or hallway through which one must pass upon
entry or exit(After faulting the entry/exit zone to reach
the keypad to disarm the system.) Since this zone
type is designed to provide an instant alarm if the
entry/exit zone is not violated first, it will protect an
area in the event an intruder hides on the premises
prior to the system being armed, or gains access to the
premises through an unprotected area.
www.PDF-Zoo.com
firealarmresources.com
Summary of Contents for VISTA-100
Page 197: ... 187 Insert DIP Switch Table Board A www PDF Zoo com firealarmresources com ...
Page 198: ... 188 Insert DIP Switch Table Board B www PDF Zoo com firealarmresources com ...
Page 199: ... 189 Insert DIP Switch Table Board C www PDF Zoo com firealarmresources com ...
Page 206: ... 196 NOTES www PDF Zoo com firealarmresources com ...