61 –
02 START PART
If the starting event will be limited to occurring on a
specific partition, enter the partition number (1-8) in
which the start event will occur. Enter 0 for any
partition. Press
✴
to continue.
02 STOP: ZN LIST
NO LIST
If a zone list is being used to stop this relay action,
enter the zone list number 1-8. The restore of a
zone on the Zone List will stop the relay. If a zone
list is not being used, enter 0. Press
✴
to continue.
02 STOP: ZN TYP
If a Zone Type/System Operation is being used to
stop the relay action, enter the 2-digit code as listed
in the start Zone Type/System Operation prompt
paragraph. Press
✴
to continue.
02 STOP PART
This is the partition to which the stop condition will
be limited. Enter 0 for any partition. Enter 1-8 for
specific partition number. Press
✴
to continue.
RELAY GROUP
Relays may be grouped for common activation by
time driven events (commands 06-10 ). Enter 0 (no
group) or 1-8 for a specific group number. Press
✴
to continue.
01 FIRE BELL?
1 = YES 0 = NO
If this relay is on a supervised 4204CF module, it
may be used as an additional fire bell. Enter 1 (Y) if
it is; enter 0 if it is not. This tells the system which
relays are to be activated during a fire drill or Fire
Walk Test. Press
✴
to continue.
RESTRICTION
1=YES 0=NO
The system may have some devices which are not
intended to be under end user control, such as
relays activating fire doors or machinery. Enter 1 if
the end user will be restricted from accessing this
relay group. If this is a fire bell, it will be restricted
automatically. Press
✴
to continue.
ECP ADDRESS
For relay modules (4204/4204CF), enter the actual
relay module's address (01-15) as set by its DIP
switches. Up to 8 modules can be installed in a
system.
MODULE RELAY #
For 4204 relay outputs, enter the specific relay
number on that module ( 1-4). For 4204CF outputs,
enter only module relay number 1 (Output A) or
relay number 3 (Output B). These are the only two
programmable relays on the 4204CF module. Press
✴
to continue.
The keypad will display the Start and Stop summary
screens again. Press
✴
to continue.
3.
When all relays have been programmed, enter 00 at the "ENTER RELAY NO."
prompt.
4.
If defining a Zone List, continue to the next section. If not, enter 00 +
✴
at the
next two prompts. You will then be asked "Quit Menu Mode?" Enter 1 for
"Yes," 0 for "No." Then enter *99 to exit programming completely.
5.
If supervision of the 4204CF relay output is desired, enter a response type for
that output's corresponding supervisory zone. This is equal to 600 + [Relay
ID No.]. For example, if you are programming Relay ID No. 1, the relay's
supervisory zone would be 601. Program this zone for response type 19 (24-
Hr. Trouble) in #93 Zone Programming mode.
www.PDF-Zoo.com
firealarmresources.com
Summary of Contents for VISTA-100
Page 197: ... 187 Insert DIP Switch Table Board A www PDF Zoo com firealarmresources com ...
Page 198: ... 188 Insert DIP Switch Table Board B www PDF Zoo com firealarmresources com ...
Page 199: ... 189 Insert DIP Switch Table Board C www PDF Zoo com firealarmresources com ...
Page 206: ... 196 NOTES www PDF Zoo com firealarmresources com ...