Remote Keypad Sounder Operation and Wiring
An optional Amseco PAL 328N piezo sounder can be used for installations where
it is desired to duplicate the sounds produced by the keypad's built-in sounder.
The panel will remote all sounds (i.e. alarm, trouble, chime, entry/exit, etc.)
produced by the keypad's built-in sounder except for the short beeps associated
with keypad key depression. One application of this feature might be to produce
chime sounds at a location which is distant from the panel's keypads. If used,
program field 3*20 must be set to "0" (factory default) to enable the remote
sounder option, and field *15 must be set to the desired partition number. The
PAL 328N must be connected to J2/OUT 5 as shown in
Figure 16.
BLACK
RED
+
–
AMSECO PAL-328N
PIEZO SOUNDER
(10MA)
1
2
3
4
5
6
7
8
9
INPUT 1
GROUND
OUT 1
OUT 4OUT 7OUT 3OUT 6OUT 2OUT 5
J2 CONNECTOR
(VIOLET)
(GRAY)
(YELLOW)
(WHITE)
(RED)
(GREEN)
(BROWN)
BLUE
BLACK
4142TR CABLE
Figure 16: Remote Keypad Sounder Wiring
Remote Keyswitch Operation and Wiring
An optional UL-listed remote keyswitch, such as the ADEMCO 4146, can be
used for remote arming/disarming of the burglary portion of the system and for
remotely silencing alarms. If used, the following must be programmed:
1.
Field *15 to assign the keyswitch to a partition (1-8), or 9 to silence fire bell if
fire alarm occurs; Enter 0 to disable.
2.
Zone 7 must be assigned a non-zero response type.
3.
Field 3*20 must be set to "1" if it is desired to use J2/OUT 1, 5 to operate
keyswitch ARMED and READY LEDs (if keyswitch provides LEDs).
4.
*40 to enable Open/Close report for keyswitch.
Wire the keyswitch as shown in
Figure 17. The tamper switch need not be used
for fire or UL Household Burglary installations. For UL Commercial Burglary
installations, the tamper switch must be wired to zone 8, and zone 8 must be
programmed for Day Trouble/Night Alarm (zone type 5). When the keyswitch is
removed from the wall, the tamper switch will open, causing an alarm or trouble
on zone 8, and causing the control to disable keyswitch operation until the
associated partition is disarmed from a keypad.
The VISTA-100 allows 2 modes of keyswitch operation. When field *15 is set to a
partition (1-8), the keyswitch operates as follows:
With System Disarmed and No Alarms Present:
A momentary short across zone 7 will arm the partition in the AWAY mode, and a
short held for more than 3 seconds will arm the partition in the STAY mode. A
subsequent short will disarm the partition. The keyswitch LEDs will indicate that
the partition has armed (see table below).
www.PDF-Zoo.com
firealarmresources.com
Summary of Contents for VISTA-100
Page 197: ... 187 Insert DIP Switch Table Board A www PDF Zoo com firealarmresources com ...
Page 198: ... 188 Insert DIP Switch Table Board B www PDF Zoo com firealarmresources com ...
Page 199: ... 189 Insert DIP Switch Table Board C www PDF Zoo com firealarmresources com ...
Page 206: ... 196 NOTES www PDF Zoo com firealarmresources com ...