![ADEMCO VISTA-100 Installation Instructions Manual Download Page 124](http://html1.mh-extra.com/html/ademco/vista-100/vista-100_installation-instructions-manual_2850251124.webp)
– 114 –
Section 22: #93 MENU MODE PROGRAMMING
This section provides the following information:
•
#93 Menu Mode main menu options
•
Zone Programming
•
Serial Number Programming
•
Report Code Programming
•
Alpha Programming
•
Device Programming
•
Relay Programming
•
Relay Voice Descriptors
•
Custom Index Programming (VIP Module substitute words)
#93 Main Menu Options
The following fields should be programmed before beginning: 2*00: Number of
Partitions; 1*32: RF receiver type.
UL
For Commercial Fire and UL Installations, verify that wireless and Audio Alarm
Verification features are disabled.
After programming all system related programming fields in the usual way, press
#93 while still in programming mode to display the first choice of the menu driven
programming options, which are as follows:
ZONE PROG?
0=No 1=Yes
For programming the following:
• Zone Number
• Zone Response Type
• Partition Number for Zone
• Dialer report code for zone
• Bell/Aux. relay assignment for zone
• Input Device Type for zone (whether RF,
polling loop, etc.)
•
Learning serial numbers of 5800 series
transmitters & serial polling loop devices into
the system (all other zone characteristics must
be pre-programmed).
SERIAL NUMBER PROG?
0=No 1=Yes
For programming the following:
•
Input Device Type for zone (whether RF,
polling loop, etc.)
•
Learning serial numbers of 5800 series
transmitters & serial polling loop devices into
the system (all other zone characteristics must
be pre-programmed).
REPORT CODE PROG?
0=No 1=Yes
For programming the following:
•
Alarm report codes for zones
•
Restore & supervisory codes
•
All other system report codes
ALPHA PROG?
0=No 1=Yes
For entering alpha descriptors for the following:
• Zone Descriptors
• Installer's Message
• Custom Words
• Partition Descriptors
• Relay Descriptors
DEVICE PROG?
0=No 1=Yes
For defining the following device characteristics for
addressable devices, including keypads, RF
receivers (4281/5881), 4204 output relay modules,
and 4285 VIP Module:
•
Device Address
•
Device Type
•
Keypad Options (incl. partition assignment)
•
RF House ID
www.PDF-Zoo.com
firealarmresources.com
Summary of Contents for VISTA-100
Page 197: ... 187 Insert DIP Switch Table Board A www PDF Zoo com firealarmresources com ...
Page 198: ... 188 Insert DIP Switch Table Board B www PDF Zoo com firealarmresources com ...
Page 199: ... 189 Insert DIP Switch Table Board C www PDF Zoo com firealarmresources com ...
Page 206: ... 196 NOTES www PDF Zoo com firealarmresources com ...