– 118 –
Learning Serial Numbers
Usually, serial numbers are learned during zone programming. If not, use #93
menu mode to learn serial numbers (for example, if all other programming was
done via downloading).
1.
Enter data field programming mode: installer code + 8 0 0 0.
2.
From data field programming mode, press #93 to display the "ZONE
PROG?" prompt.
3.
Press 0 (NO) repeatedly until the "SERIAL # PROG?" prompt appears.
SERIAL # PROG?
0=no 1=yes
To learn or delete a device's serial number, enter 1
(yes). Enter 0 to move to skip to the next main menu
option.
Enter Zone No.
00=QUIT
Enter the zone number of the device to be learned or
deleted. Press
✴
to move to the next prompt.
Enter 00 to quit Serial Number programming.
If that zone number was programmed as a non-
applicable input type (i.e., Hardwird) in the Zone
Programming mode, a prompt indicating such will
appear. Press
✴
to return to the "Enter Zone No."
prompt.
010 PROG AS RF:2
A000-5372:2
If a serial number has already been learned for that
device, a summary prompt will appear displaying the
type of device and its serial number. Press
✴
to
continue to the Delete S/N prompt.
DELETE S/N?
0=No, 1=Yes
Enter 1 to delete the displayed serial numbered
device. Enter 0 if this device should not be deleted.
Input type
Input = 0 or 3-6
If a serial number for that device has not been
learned yet, and if the device assigned to that zone
number has been programmed as a serial number
input device in the Zone Programming menus, this
prompt will appear. Enter the device input type as
follows: 0=none, 3= supervised RF transmitter (RF
type), 4 = unsupervised RF transmitter (UR), 5= RF
button type (BR type), 6 = serial polling loop device
(SL type). Press
✴
to continue.
Learn S/N?
0=No, 1=Yes
If adding a new serial number device to the system,
this prompt will appear after entering the input type.
Enter 1 to learn the device's serial number into the
system. Press
✴
to continue.
www.PDF-Zoo.com
firealarmresources.com
Summary of Contents for VISTA-100
Page 197: ... 187 Insert DIP Switch Table Board A www PDF Zoo com firealarmresources com ...
Page 198: ... 188 Insert DIP Switch Table Board B www PDF Zoo com firealarmresources com ...
Page 199: ... 189 Insert DIP Switch Table Board C www PDF Zoo com firealarmresources com ...
Page 206: ... 196 NOTES www PDF Zoo com firealarmresources com ...