– 180 –
Trouble Conditions
Supervisory Messages
• A display of “SUPV” accompanied by a zone number (001-087) and an
alpha descriptor (if programmed) indicates that a fire supervisory
condition exists on that zone. This means that the operation of the fire
alarm system may be compromised.
Check or Trouble Messages
• A display of "CHECK" or "TRBL" (as per field 3*00) accompanied by a
zone number (001-087) and an alpha descriptor descriptor indicates that
a problem exists with that zone. Zone trouble may be caused by one of
the following conditions:
--A hardwired fire zone is open (broken wire)
--A Day/Night zone (Zone Type 5) is faulted
--A polling loop zone is not seen by the control panel
--A polling loop zone has been tampered (cover removed on a 4190)
--A wireless zone has not checked in during the time programmed in
field 1*31
--A 5800 series transmitter has been tampered (cover removed)
• "CHECK" accompanied by a numeric display of "6XX," where XX = 01-16,
indicates a trouble on a 4204CF supervised bell output (corresponding
relay number 01-16)
• "CHECK" accompanied by a numeric display of "8XX," where XX = 00-31,
indicates a trouble on a peripheral device (connected to the panel's
keypad terminals) of the corresponding device address (00-31)
• "CHECK" accompanied by a numeric display of "9XX," where XX = 00-99,
indicates that a system trouble exists (dialers, bell outputs, ground fault,
etc). See the Zone Index section.
If the problem has been corrected, key an OFF sequence (Security Code plus
OFF) twice to clear the display.
Other System Messages
• "COMM. FAILURE" at the keypad
Indicates that a failure occurred in the telephone communication portion
of your system.
• "LO BAT" and a zone descriptor, accompanied by a once per minute beep
at the Keypad
Indicates that a low battery condition exists in the wireless transmitter
displayed. The audible warning sound may be silenced by pressing any
key.
• "SYSTEM LO BAT"
Indicates that a low battery condition exists with the system's backup
battery.
www.PDF-Zoo.com
firealarmresources.com
Summary of Contents for VISTA-100
Page 197: ... 187 Insert DIP Switch Table Board A www PDF Zoo com firealarmresources com ...
Page 198: ... 188 Insert DIP Switch Table Board B www PDF Zoo com firealarmresources com ...
Page 199: ... 189 Insert DIP Switch Table Board C www PDF Zoo com firealarmresources com ...
Page 206: ... 196 NOTES www PDF Zoo com firealarmresources com ...