– 191 –
SPECIFICATIONS
VISTA-100 CONTROL
Physical:
18”H X 14.5”W X 4.3”D
Electrical:
Primary Power:
From Ademco No. 1451 Transformer with enclosure; rated 18VAC, 72VA
Backup Battery:
12VDC, 12AH min to 34.4AH max lead acid battery (gel type)
Alarm Power:
12VDC, 1.7 amps max for each bell output
Aux. Standby Pwr: 12VDC, 1 amp max
Total Power:
Combined auxiliary standby and alarm currents must not exceed 2.3 amps
Standby Time:
24 hours with 1 amp aux. standby load or 60 hours with 205mA aux. standby load using 34.4AH
battery
Fusing:
Battery input, auxiliary and bell power outputs are protected using PTC circuit protectors. All
outputs are power limited
Main Dialer:
Line Seize:
Double Pole
Ringer Equiv.:
0.7B
FCC Registration: AC398U-68192-AL-E
TLM Threshold:
Good line when tip to ring voltage greater than approx. 25V (13V when blue jumper cut) or when
handset current greater than approx. 10mA. Bad line when both voltage and current below these
levels.
Formats:
Ademco Low Speed, Ademco 4+2 Express, Ademco High Speed, Ademco Contact ID, Sescoa and
Radionics
Agency Listings:
Burglary:
UL609 Grade A Local Mercantile Premises and Mercantile Safe and Vault
UL611/UL1610 Grades A, AA Central Station
UL365 Grades A, AA Police Connect
Fire:
UL864-NFPA 72 Local, Central Station, and Remote Station
5140DLM BACKUP DIALER MODULE
Physical:
2.75”H X 4”W X 1”D
Mounts on VISTA-100 main PC board shield using standoffs supplied
Misc.:
Connects to VISTA-100 main PC board J3 header using ribbon cable supplied.
FCC Registration: AC398U-62668-MO-N
5140LED ANNUNCIATOR MODULE
Physical:
4.5”H X 2.75”W X 1.5”D
Mounts to single gang electrical box
Indicators:
AC Power, Comm Failure, Dialer 1 Fault and Dialer 2 Fault.
Connect indicator inputs to VISTA-100 trigger outputs (J2 header)
DIGITAL COMMUNICATOR
FORMATS SUPPORTED:
ADEMCO HIGH SPEED
ADEMCO 4+2 EXPRESS
ADEMCO LOW SPEED
ADEMCO CONTACT ID
SESCOA
RADIONICS LOW SPEED
LINE SEIZE : Double Pole
RINGER EQUIVALENCE: 0.7B
FCC REGISTRATION NO .: AC398U-68192-AL-E
6139(R) Remote Keypad
Physical:
Width: 6.25 inches
Height: 4.75 inches
Depth: 1.25 inches (6137 = 1 inch )
Electrical : Voltage Input: 12VDC
Current Drain: 100 mA, reduces to 40mA
when control is operating in standby mode
from backup battery only.
Interface Wiring for Keypads:
RED: 12VDC input (+) auxiliary power
BLUE: Not Used
GREEN: Data to control panel
YELLOW: Data from control panel
BLACK: Ground and (-) connection from
supplemental power supply.
www.PDF-Zoo.com
firealarmresources.com
Summary of Contents for VISTA-100
Page 197: ... 187 Insert DIP Switch Table Board A www PDF Zoo com firealarmresources com ...
Page 198: ... 188 Insert DIP Switch Table Board B www PDF Zoo com firealarmresources com ...
Page 199: ... 189 Insert DIP Switch Table Board C www PDF Zoo com firealarmresources com ...
Page 206: ... 196 NOTES www PDF Zoo com firealarmresources com ...