Time-Driven Event Worksheet
These are the schedules used to activate outputs, bypass zones, etc. based on a
time schedule. There are 20 of these events that may be programmed for the
system, with each event governed by the previously defined time windows.
The actions that can be programmed to automatically activate at set times are
relay commands, arm/disarm and zone bypassing commands, and open/close
access conditions.
To fill out the worksheet:
1)
First enter the schedule number (01-20) and time window number (01 -
20), and note the day of the week the action is desired.
2)
Enter the code for the desired action and action specifier. The action
codes are the events that are to take place when the scheduled time is
reached. Each action also requires an action specifier, which defines what
the action will affect (relay, relay group, partition, zone list, user group). The
action specifier varies, depending on the type of action selected.
The following is a list of the "Action" codes (desired actions) used when
programming time driven events. Note that these codes are independent of
the "relay codes" programmed during the #93 Menu Mode–Relay
Programming mode.
Relay commands
Action Code
Action Specifier
01 Relay On
Relay #
02 Relay Off
Relay #
03 Relay Close for 2 seconds
Relay #
04 Relay Close XX minutes (set in field 1*74)
Relay #
05 Relay Close YY seconds (set in field 1*75)
Relay #
06 Relay Group On
Relay Group #
07 Relay Group Off
Relay Group #
08 Relay Group Close for 2 seconds
Relay Group #
09 Relay Group Close XX minutes (set in field 1*74)
Relay Group #
10 Relay Group Close YY seconds (set in field 1*75)
Relay Group #
Arm/Disarm commands
Activation times 1 (Beginning), 2 (End), 3 (During) are the only valid choices
for automatic arming and disarming functions.
"During" can be used to arm or disarm the control for specific time only. For
example, if "during" is selected with arm-stay, the system will arm-stay at the
beginning of the window and disarm at the end of the window.
Action Code
Action Specifier
20 Arm-Stay
Partition(s)
21 Arm Away
Partition(s)
22 Disarm
Partition(s)
23 Force Arm Stay (Auto-bypass faulted zns)
Partition(s)
24 Force Arm Away (Auto-bypass faulted zns)
Partition(s)
The auto-arm warning (field 2*06) applies.
Bypass commands
Activation times 1 (Beginning), 2 (End), 3 (During) are the only valid choices
for bypass commands. If 3 (During) is selected for auto-bypassing, the
system will bypass the zone(s) specified on a particular Zone List at the
beginning of the window and unbypass the zone(s) at the end of the window.
If it is selected for auto unbypassing, the system will remove the bypass of
the zone(s) at the beginning of the window and will restore the bypass of the
zone(s) at the end of the window.
www.PDF-Zoo.com
firealarmresources.com
Summary of Contents for VISTA-100
Page 197: ... 187 Insert DIP Switch Table Board A www PDF Zoo com firealarmresources com ...
Page 198: ... 188 Insert DIP Switch Table Board B www PDF Zoo com firealarmresources com ...
Page 199: ... 189 Insert DIP Switch Table Board C www PDF Zoo com firealarmresources com ...
Page 206: ... 196 NOTES www PDF Zoo com firealarmresources com ...