The 4100SM module is supplied with a 10 foot RS232 cable. A longer cable or
an extension cable can be used if the VISTA-100 and serial printer are separated
by more than 10 feet, but the total cable length should be less than 50 feet.
The 4100SM module must be connected to the panel using the distance of the
trigger cable. The wires
cannot
be lengthened to mount the module in a remote
location.
Most printers either ignore the CTS, DSR and CD signals, or require them to be
high (i.e. 3-15VDC as measured on RS232 DB25 connector pins 5, 6 & 8
respectively with respect to ground pin 7). The 4100SM module sets these pins
high. If the printer being used will not operate with these pins high, then clip the
blue (CTS), white (DSR) or red (CD) jumpers on the 4100SM module to set the
corresponding signal floating. Important pins on the RS232C cable are pin 3
(data out), pin 7 (ground) and pin 20 (DTR - ready).
The DTR signal, as measured at 4100SM TB1, should be high (9.5-14VDC) when
the printer is powered, properly connected, on-line and ready to print. This signal
will be low (0-1.5VDC) when the printer is not powered, not properly connected, off -
line or out of paper. The VISTA-100 will not send printing data to the printer unless
the DTR signal is high.
Programming Event Log Options
1.
With at least one alpha keypad (6139/6139R) wired and set to a proper
address, temporarily apply power to the system.
2.
Enter data field programming mode: [Installer Code] + 8 0 0 0.
Program the following data fields:
1*70 EVENT LOG TYPES ( 1=enable; 0=disable for each type)
1*71 12/24 HOUR TIME STAMP FORMAT (0=12hr; 1=24hr)
1*72 EVENT LOG PRINTER ON-LINE ( 0=disable; 1=enable)
1*73 PRINTER BAUD RATE (1=300; 0=1200)
3.
Enter #93 Report Code Programming mode to program report codes for
the event log (System Group #4 codes) .
4.
Exit program mode by pressing *99.
If you need more information about actual programming procedures, see Section
4:
THE MECHANICS OF PROGRAMMING.
Event Logging Procedures
In order for proper time and date stamping to occur, the system's real-time clock
must be set. Refer to the
SETTING THE REAL TIME CLOCK
section.
If you have selected the printer to be "on-line" (field 1*72), events will print
automatically, as they occur. To display or print on demand, the following
commands apply:
Commands
Display Mode:
Installer or Master Code + [#] + [6] + [0]
Print Mode:
Installer or Master Code + [#] + [6] + [1]
Clear Event Log:
Installer or Master Code + [#] + [6] + [2]
To EXIT Event Log:
Press
✴
at any time.
www.PDF-Zoo.com
firealarmresources.com
Summary of Contents for VISTA-100
Page 197: ... 187 Insert DIP Switch Table Board A www PDF Zoo com firealarmresources com ...
Page 198: ... 188 Insert DIP Switch Table Board B www PDF Zoo com firealarmresources com ...
Page 199: ... 189 Insert DIP Switch Table Board C www PDF Zoo com firealarmresources com ...
Page 206: ... 196 NOTES www PDF Zoo com firealarmresources com ...