– 57 –
4.
Press 0 (NO) to each menu option until the "DEVICE PROG?" prompt
appears.
DEVICE PROG?
1=YES 0=NO
Press 1 (YES) to enter DEVICE PROGRAMMING mode.
The following prompts will appear.
DEVICE ADDRESS
01-31, 00=QUIT
The device address identifies the module to the control.
Enter the 2-digit address number as set at the module's
DIP switches ( 01-15). Press
✴
to continue.
DEVICE TYPE
Select the (relay) output device as follows:
00 =device not used
04= output device
Press
✴
to continue.
SUPERVISED CF?
If the relay module is a 4204CF, enter 1. If not, enter 0.
If 1 is entered, only relay 1 (Output A) and relay 3
(Output B) on each module are able to be programmed
for functions. This module is usually used to add two
additional supervised bell outputs to the system.
Press
✴
to continue.
DEVICE ADDRESS
01-31, 00=QUIT
Repeat the procedure above for each relay module used
in the system. When all modules have been
programmed, press 00
✴
to exit Device Programming
mode.
QUIT MENU MODE?
1 = YES 0 = NO
Press 1 (Y) to return to the data field programming
mode or (0) to access other menu options. To
program relay functions, continue to the next
section.
5.
If supervision of the module is desired, enter a response type for the
module's corresponding supervisory zone. This is equal to 800 + [Device
Address]. For example, if the 4204 is set and programmed as Device
Address 03, the module's supervisory zone would be 803. Program this
zone for response type 19 (24-Hr. Trouble) or 05 (Trouble-by-Day, Alarm-by -
Night) in #93 Zone Programming mode.
Output Programming Options Defined
The following will help you understand the programming of OUTPUT DEVICES
when using the #93 Relay Programming mode. The options used to start and
stop these devices are described below, followed by the actual screen prompts
and available entries.
The letter(s) in parentheses after each function described below, such as (A)
after ACTION, are those that appear in the various summary displays of
programmed data during programming.
ACTION (A)
The "ACTION" of the device is how the device will respond
when it is activated by the "START" programming. You may
want the device to activate momentarily, to pulse on and off
continuously, or to remain activated until some other event
occurs to stop it. There are four different choices of actions:
•
ACTIVATE for 2 SECONDS and then reset.
•
ACTIVATE and REMAIN ACTIVATED until stopped by
some other event.
•
PULSE ON and OFF until stopped by some other event.
www.PDF-Zoo.com
firealarmresources.com
Summary of Contents for VISTA-100
Page 197: ... 187 Insert DIP Switch Table Board A www PDF Zoo com firealarmresources com ...
Page 198: ... 188 Insert DIP Switch Table Board B www PDF Zoo com firealarmresources com ...
Page 199: ... 189 Insert DIP Switch Table Board C www PDF Zoo com firealarmresources com ...
Page 206: ... 196 NOTES www PDF Zoo com firealarmresources com ...