– 111 –
2*18
ENABLE GOTO FOR THIS PARTITION
[0]
(partition-specific)
Enter 1 if this partition is to be accessed from another partition's keypad
using the GOTO command. Otherwise enter 0.
2*19
USE PARTITION DESCRIPTORS
[1]
Enter 1 if partition descriptors will be programmed. If enabled, the normal
keypad display will include a partition number and four-digit descriptor).
Enter 0 to cause the keypads to display a non-partitioned system type of
display (no partition number will appear).
2*20
ENABLE J2 TRIGGERS BY PARTITION
[1]
(partition-specific)
2*21
SUPERVISION PULSES FOR LORRA
[000] | |
TRIGGER OUTPUTS
F B S
Used for supervised connection to 7920SE.
Enter 1 to enable pulses for each type of LORRA trigger (burglary, fire,
silent panic). This option causes the control to send periodic short pulses
on the J2 radio triggers These pulses are used by the 7920SE to
determine that its connection to the control is still intact. Enter 0 if not
desired. Must be 1 for Commercial fire and UL.
2*22
DISPLAY FIRE ALARMS
[0]
OF OTHER PARTITIONS (partition-specific)
Enter 1 to allow fire alarms that occur on other partitions to be displayed
at this partition's keypad(s). Otherwise, enter 0.
2*23
DISPLAY BURG & PANIC ALARMS [0]
OF OTHER PARTITIONS
Enter 1 to allow burglary and panic alarms that occur on other partitions
to be displayed at this partition's keypad(s). Otherwise, enter 0.
2*24
DISPLAY TROUBLES
[0]
OF OTHER PARTITIONS
Enter 1 to allow troubles that occur on other partitions to be displayed at
this partition's keypad(s). Otherwise, enter 0.
3*00
DISPLAY TRBL INSTEAD OF CHECK
[0]
Enter 1 to display the letters TRBL instead of CHECK when a zone or
system trouble occurs. Enter 0 to display CHECK.
3*13
SUPV. N.O./N.C. SELECTION
[0]
Enter 0 if you want a supervisory response on a shorted zone and a
trouble response on an open zone. Enter 1 if you want a supervisory
response on either a shorted or an open zone.
3*14
WATERFLOW SILENCE OPTION
[1]
Enter 0 if you want Waterflow Supervisory zones to be silenced by
entering the Code + OFF. Enter 1 if you want Waterflow Supervisory
zones to silence automatically when waterflow ceases. This feature may
only be set to "1" by permission of the local authority.
www.PDF-Zoo.com
firealarmresources.com
Summary of Contents for VISTA-100
Page 197: ... 187 Insert DIP Switch Table Board A www PDF Zoo com firealarmresources com ...
Page 198: ... 188 Insert DIP Switch Table Board B www PDF Zoo com firealarmresources com ...
Page 199: ... 189 Insert DIP Switch Table Board C www PDF Zoo com firealarmresources com ...
Page 206: ... 196 NOTES www PDF Zoo com firealarmresources com ...