– 59 –
STOP (STP):
The "STOP" programming determines when and under what
conditions the device will be de-activated. The following
options are available:
A)
1.
RESTORE ZONE LIST (ZL) . If a "ZONE LIST" is used as the
“Stop” event, the device will de-activate when all the zones in
that list restore from a previous fault, trouble, or alarm
condition. This will occur regardless of what is programmed
to "START" the device; therefore, a "RESTORE ZONE LIST"
would nor mally only be used when a "ZONE LIST" is used to
start the device.
B).
1.
ZONE TYPE/SYSTEM OPERATION (ZT). Instead of using a
"RESTORE ZONE LIST", a specific zone (response) type or
system operation action can be selected to de-activate the
device.
If a specific "ZONE TYPE" is chosen, any zone of that
response type that restores from a previous alarm, trouble, or
fault condi tion will cause the device to de-activate.
If a "SYSTEM OPERATION" is chosen, that operation will
cause the device to de-activate. The different choices for
"ZONE TYPE" and "SYSTEM OPERATION" are listed in
“Programming Relays” later in this section, and in the
Programming Form.
2.
PARTITION No. (P). The device's "Stop" Zone Type/System
Operation may be limited to an occurrence on one partition
(1-8), or any partition (0).
Programming Output Devices
1.
From data field programming mode, press #93 to display the "ZONE
PROG?" prompt.
2.
Press 0 (NO) to each menu option until the " RELAY PROG? " prompt
appears. Press 1 (YES).
While in this mode, press
✴
to advance to next screen. Press # to backup
to the previous screen.
ENTER RELAY NO.
(00=QUIT) 01
Enter the relay (output device) identification number
01-16 . This is a reference number only, used for
identification purposes. The actual module address
and relay number on the module are programmed in
the last two prompts. Press
✴
to continue.
02 A EV ZL ZT P
STT 0 0 0 00
The keypad will display a summary START screen.
Press
✴
to continue.
02 A ZL ZT P
STP 0 0 00
The keypad will display a summary STOP screen.
Press
✴
to continue.
02 RELAY ACTION
NO RESPONSE
The Relay Action is the way in which the relay will
respond when activated by the "start" event. Enter
the desired action for this relay as follows:
0=not used; 1 =close for 2 secs.; 2=stay closed;
3=pulse on/off
www.PDF-Zoo.com
firealarmresources.com
Summary of Contents for VISTA-100
Page 197: ... 187 Insert DIP Switch Table Board A www PDF Zoo com firealarmresources com ...
Page 198: ... 188 Insert DIP Switch Table Board B www PDF Zoo com firealarmresources com ...
Page 199: ... 189 Insert DIP Switch Table Board C www PDF Zoo com firealarmresources com ...
Page 206: ... 196 NOTES www PDF Zoo com firealarmresources com ...