ENABLE DIALER REPORTS
[0]
FOR PANICS & DURESS (partition-specific)
95 96 99 Duress
Enter 1 for each panic/duress for which reporting is desired.
*87
ENTRY WARNING (partition-specific)
[0]
Enter 0 for 3 short beeps, or 1 for slow beeps that continue for the entire
entry delay period.
*88
BURG. ALARM COMM. DELAY (partition-specific)
[0] |
Enter 0 for no delay on burglary alarm communication. Enter 1 for 16-
second delay (no delay on 24-hour reports). Must be 0 for UL
installations.
*89
RESTORE REPORT TIMING
[0]
Enter 0 for instant restore report as zone restores.
Enter 1 for reporting after bell timeout if zone restored. Enter 2 for
restore report when system is subsequently disarmed. Must be 2 for
Commercial Fire or UL Commercial Burglary installation.
*90
SECONDARY SUBSCRIBER ACCT #
| | | |
(partition-specific)
Enter 00-09; B-F (11-15) [15 15 15 15]
Enter the 3 or 4 digit number (depending on report format) for the
secondary subscriber account, 00-09; B-F (11-15). Each number requires
a 2-digit entry so as to allow entry of hexadecimal digits (B-F). If a 3-digit
number is to be used, only enter data in the first 6 locations, leaving the
last two unfilled. Default=15 15 15 15. Erase the field by entering *90*.
NOTE: This field
must be programmed if a secondary phone number is
used (field *34). This account number can be the same as the primary
account number.
1*17
LOBBY PARTITION
[0]
Enter the common lobby partition (1-8).
Enter 0 if none.
1*18
AFFECTS LOBBY (partition-specific)
[0]
Enter 1 if this partition affects the common lobby. Will cause lobby to
disarm when this partition disarms.
Enter 0 if it does not.
1*19
ARMS LOBBY (partition-specific)
[0]
Enter 1 if arming this partition causes the system to attempt to arm the
common lobby partition automatically. Can only arm lobby if all other
affecting partitions are armed. To enable this field, field 1*18 must also
be enabled. (partition-specific)
Enter 0 if arming this partition will not attempt to arm the common lobby
partition.
1*20
EXIT ERROR LOGIC
[0]
Enter 1 to enable Exit Error Logic (entry/exit doors will be bypassed if left
open).
Enter 0 if Exit Error Logic is not desired. Must be 0 for UL Commercial
Burglary installations.
1*21
EXIT DELAY RESET
[0]
Enter 1 to reset Exit Delay to 60 seconds after door is closed.
Enter 0 if Exit Delay not to be reset. Must be 0 for UL Commercial
Burglary installations.
www.PDF-Zoo.com
firealarmresources.com
Summary of Contents for VISTA-100
Page 197: ... 187 Insert DIP Switch Table Board A www PDF Zoo com firealarmresources com ...
Page 198: ... 188 Insert DIP Switch Table Board B www PDF Zoo com firealarmresources com ...
Page 199: ... 189 Insert DIP Switch Table Board C www PDF Zoo com firealarmresources com ...
Page 206: ... 196 NOTES www PDF Zoo com firealarmresources com ...