–28–
Compatible Glass Break Detectors
Use detectors that meet the following ratings:
Standby Voltage:
5VDC–13.8VDC
Standby Resistance: Greater than 20k ohms (equivalent resistance of all
detectors in parallel)
Alarm Resistance:
Less than 1.1k ohms (see note below)
Alarm Current:
2 mA–10 mA
Reset Time:
Less than 6 seconds
The IEI 735L series detectors have been tested and found to be compatible
with these ratings. You can use up to fifty IEI 735L detectors connected in
parallel.
1. The alarm current provided by zone 8 will support only one Glass Break
detector in the alarmed state.
2. Do not use other N.O. or N.C. contacts when using glass break detectors
on zone 8. Other contacts may prevent proper glass break detector
operation.
You can use detectors which exceed 1.1k ohms in alarm, provided they
maintain a voltage drop in alarm of less than 3.8 volts.
Programming Hardwired Zones
1.
With at least one two-line alpha keypad (6139/6139R) wired and set to a
proper address (00-30), temporarily apply power to the system.
2.
Enter data field programming mode: [Installer Code] + 8 0 0 0 and
program the following data fields:
*41 EOLR DISABLE FOR ZONES 3-8 (1 =N.C. loops; 0 =EOLR)
2*00 NUMBER OF PARTITIONS (1-8) if you haven't already done this in
previous section.
3.
From data field programming mode, press #93 to display the "ZONE
PROG?" prompt.
ZONE PROG?
1=YES 0=NO
Press 1 to enter ZONE PROGRAMMING mode.
While in this mode, press
✴
to display the next
screen, or press # to display the previous screen.
ENTER ZN NO.
000=QUIT 002
Enter the zone number to be programmed 001-008.
Press
✴
to continue.
002 ZT P RC B In:L
00 1 00 0 HW:N
A summary screen for that zone will appear. ZT =
zone type; P= partition to which zone is assigned;
RC = report code for zone; B = bell/relay select for
zone; In = input type of zone; L = Loop number
(applies only to 5800 series RF zones).
Press
✴
to continue.
www.PDF-Zoo.com
firealarmresources.com
Summary of Contents for VISTA-100
Page 197: ... 187 Insert DIP Switch Table Board A www PDF Zoo com firealarmresources com ...
Page 198: ... 188 Insert DIP Switch Table Board B www PDF Zoo com firealarmresources com ...
Page 199: ... 189 Insert DIP Switch Table Board C www PDF Zoo com firealarmresources com ...
Page 206: ... 196 NOTES www PDF Zoo com firealarmresources com ...