– 104 –
*50
SESCOA/RADIONICS SELECT
[0]
Enter 0 if Radionics format is to be used with hexadecimal 0-9, B-F
reporting. Enter 1 if SESCOA format is to be used with only numeric
reporting (0-9). Note that selection applies to both primary and secondary
phone numbers.
*51
DUAL REPORTING
[0]
This field allows all reports to be sent to both primary and secondary
phone numbers.
Enter 1 if all reports are to be sent to both primary and secondary phone
numbers. If used with Split Reporting option 1 (1*34), alarms go to both
primary & secondary numbers, while all other reports go to secondary
only. If used with Split Reporting option 2 , alarms go to both lines,
open/close and test messages go to secondary only, while all other
reports go to primary. If used with Split Reporting option 3, fire alarms
and supervisories go to primary, all reports go to secondary.
*52
STANDARD/EXPANDED REPORT PRIMARY
Alm
Rst
Byp
Trbl Opn/Cls Low Batt
Enter 0 for standard or 1 for expanded reporting for the primary phone
number; default is 0 .
Note: Expanded overrides 4+2 format.
*53
STANDARD/EXPANDED REPORT SECONDARY
Alm
Rst
Byp
Trbl Opn/Cls Low Batt
Enter 0 for standard or 1 for expanded reporting for the secondary phone
number; default is 0 .
Note: Expanded overrides 4+2 format.
*79
ZONE TYPE RESTORES FOR ZONE TYPES 1-8
1
2
3
4
5
6
7
8
Enter 1 to enable restore reporting for individual zone types.
Enter 0 if no restore report is desired for a zone type.
*80
ZONE TYPE RESTORES FOR TYPES 9/10
9
10
Enter 1
to enable restore reporting for individual zone types.
Enter 0 if no restore report is desired for a zone type.
*83
FIRST TEST REPORT TIME
| | |
Enter the day ( 00-07) and time ( 00-23 hours/00-59 min. ) that the first
test report shall be transmitted.
00 entry in all locations signifies immediately upon exiting.
00 entry in the day location will cause the report to be sent at the next
occurrence of the time that is set.
Note that day 01=Monday. See
Section 22: REPORT CODE
PROGRAMMING (System Group 1) for assigning the Test report code.
*84
SWINGER SUPPRESSION (partition-specific)
[15] |
This option limits the number of messages (Alarms or Troubles) sent for
a specific channel in an armed period (Swinger Suppression). Enter 01-
15. If 00 is selected, all Alarm or Trouble codes are reported.
Must be 00 (disabled) for Commercial Fire and UL installations.
www.PDF-Zoo.com
firealarmresources.com
Summary of Contents for VISTA-100
Page 197: ... 187 Insert DIP Switch Table Board A www PDF Zoo com firealarmresources com ...
Page 198: ... 188 Insert DIP Switch Table Board B www PDF Zoo com firealarmresources com ...
Page 199: ... 189 Insert DIP Switch Table Board C www PDF Zoo com firealarmresources com ...
Page 206: ... 196 NOTES www PDF Zoo com firealarmresources com ...