8 Maintenance
8.1 Required maintenance activities
Test the motor contactors for a protective stop
Verify that a protective stop opens the motor contactors.
Note
Action
In automatic mode, make SafeMove trigger a pro-
tective stop. For example, a stop issued from a safe
fieldbus or a zone violation.
1
Verify that the event log
90523 Safety Controller
Protective Stop triggered
is shown on the FlexPend-
ant.
2
Verify that it is not possible to close the motor con-
tactors, that is, go to state motors on.
3
Verify that the contacts on the panel board are connected as intended
DANGER
If any of the contacts X1, X2, X5, or X6 on the panel board are jumpered, the
SafeMove functionality will not provide any safety.
See
Validate the configuration on page 173
Internal functions are self tested
All internal functionality in the SafeMove safety controller is subject to self tests
and requires no maintenance activities.
Application manual - Functional safety and SafeMove2
193
3HAC052610-001 Revision: P
© Copyright 2016-2020 ABB. All rights reserved.
8 Maintenance
8.1 Required maintenance activities
Summary of Contents for SafeMove2
Page 1: ...ROBOTICS Application manual Functional safety and SafeMove2 ...
Page 8: ...This page is intentionally left blank ...
Page 16: ...This page is intentionally left blank ...
Page 34: ...This page is intentionally left blank ...
Page 56: ...This page is intentionally left blank ...
Page 72: ...This page is intentionally left blank ...
Page 112: ...This page is intentionally left blank ...
Page 194: ...This page is intentionally left blank ...
Page 196: ...This page is intentionally left blank ...
Page 234: ...This page is intentionally left blank ...
Page 237: ......