Auto-reclosing - Single- and/or
three-phase
ABB Network Partner AB
1MRK 580 170-XEN
Page
5 - 65
Version 1.0-00
After the reclaim time, the AR state control resets to the original rest state,
with AR01-SETON = 1, AR01-READY = 1 and AR01-P1PH = 1 outputs
(depending on the selected program). The other outputs are = 0.
2.3.11Permanent fault
After reclosing, a new trip is made and a new AR01-START or AR01-
TRSOTF signal appears, which means Trip Int. into the logic. It acti-
vates AR01-UNSUC (Reclosing unsuccessful). The timers for the 1, t1S
and t1 reclosing shot cannot be started (Fig. 5).
Depending on the setting of the parameter PulseCut, the closing command
may be shortened at the second tripping command.
After time-out of the reclaim timer, the function resets, but the breaker
remains open (AR01-CBCLOSED = 0, AR01-CBREADY = 1), meaning
that the reclosing function is not ready for a new reclosing function. See
Fig. 3 and Fig. 8.
2.3.12More details about
reclosing programs
3ph
3-phase, single-shot reclosing.
The output AR01-P3PH is always high (=1).
A tripping operation is made as a three-phase trip at all fault types.
The reclosing is as a three-phase reclosing in program 1/3ph, described
earlier.
2*3ph
3-phase + 3-phase, two-shot reclosing.
The operation is similar to that in program 3ph, but at a tripping after the
first reclosing shot, a second reclosing shot is made.
3*3ph and 4*3ph
They are as the 2-shot reclosing program 2*3ph, but 3 or 4 shots are
made.
1ph
1-phase, single-shot reclosing.
At 1-phase tripping, the operation is as described in program 1/3ph. At
receipt of the three-phase trip signal AR01-TPTRIP, the reclosing is inter-
rupted and blocked for the tInhibit set inhibit time.
1ph + 3ph
1-phase+ 3-phase two-shot reclosing, or 3-phase single-shot reclosing.
For a multi-phase fault and a three-phase tripping, the operation is as in
program 1/3ph, one reclosing shot is made.
But at a single-phase fault and a single-phase tripping and reclosing, a
second three-phase reclosing with a longer delay is made. Three separate
AR open time timers are used, t1S or t1 for the first shot, and t2 for the
second shot (1-300 s).
Fig. 9 illustrates the sequence.
Summary of Contents for REC 561
Page 19: ...ABB Network Partner AB Introduction REC 561 Version 1 0 00 1MRK 580 146 XEN Page 2 14 ...
Page 31: ...ABB Network Partner AB Requirements and basic technical data REC 561 Version 1 0 00 Page 2 26 ...
Page 49: ...ABB Network Partner AB Page IV ...
Page 121: ...ABB Network Partner AB Menu tree Appendix Version 1 0 00 1MRK 580 158 XEN Page 3 72 ...
Page 139: ...ABB Network Partner AB Terminal identification Version 1 0 00 1MRK 580 160 XEN Page 4 4 ...
Page 143: ...ABB Network Partner AB Activation of setting group Version 1 0 00 1MRK 580 162 XEN Page 4 8 ...
Page 175: ...ABB Network Partner AB Configurable logic Version 1 0 00 1MRK 580 161 XEN Page 4 40 ...
Page 385: ...ABB Network Partner AB Apparatus control Version 1 0 00 1MRK 580 150 XEN Page 6 100 ...
Page 495: ...ABB Network Partner AB Interlocking Version 1 0 00 1MRK 580 151 XEN Page 6 210 ...
Page 515: ...ABB Network Partner AB Event function Version 1 0 00 1MRK 580 140 XEN Page 6 230 ...
Page 519: ...ABB Network Partner AB Page IV ...
Page 561: ...ABB Network Partner AB Time synchronisation Version 1 0 00 1MRK 580 135 XEN Page 7 42 ...
Page 569: ...ABB Network Partner AB Internal events Version 1 0 00 1MRK 580 134 XEN Page 7 50 ...
Page 599: ...ABB Network Partner AB Index Version 1 0 01 1MRK 580 175 XEN Page 8 6 ...
Page 634: ......
Page 635: ......
Page 636: ......
Page 637: ......
Page 638: ......
Page 639: ......
Page 640: ......
Page 641: ......
Page 642: ......
Page 643: ......