ABB Network Partner AB
Interlocking
Version 1.0-00
1MRK 580 151-XEN
Page 6
-
116
For a line bay in section 2, the same conditions as above are valid by
changing section 1 to section 2 and vice versa.
4.2.1.3 Parameter setting
If there is no bypass busbar and therefore no Q7 disconnector, then the
interlocking for Q7 is not used. The states for Q7, Q75, C_DC, BC_AC,
BC_BC are set to open by setting the appropriate module inputs as fol-
lows. In the functional block diagram, 0 and 1 are designated 0=FIXD-
OFF and 1=FIXD-ON:
• Q7_OP = 1
• Q7_CL = 0
• Q75_OP = 1
• Q75_CL = 0
• C_DC_OP = 1
• C_DC_CL = 0
• BC_AC_OP = 1
• BC_AC_CL = 0
• BC_BC_OP = 1
• BC_BC_CL = 0
• EXDU_BPB = 1
• VP_C_DC = 1
• VP_BC_AC = 1
• VP_BC_BC = 1
If there is no second busbar B and therefore no Q2 disconnector, then the
interlocking for Q2 is not used. The state for Q2, Q25, BC_AB, BC_BC
are set to open by setting the appropriate module inputs as follows. In the
functional block diagram, 0 and 1 are designated 0=FIXD-OFF and
1=FIXD-ON:
• Q2_OP = 1
• Q2_CL = 0
• Q25_OP = 1
• Q25_CL = 0
• BC_AB_CL = 0
• BC_BC_OP = 1
• BC_BC_CL = 0
• VP_BC_AB = 1
Summary of Contents for REC 561
Page 19: ...ABB Network Partner AB Introduction REC 561 Version 1 0 00 1MRK 580 146 XEN Page 2 14 ...
Page 31: ...ABB Network Partner AB Requirements and basic technical data REC 561 Version 1 0 00 Page 2 26 ...
Page 49: ...ABB Network Partner AB Page IV ...
Page 121: ...ABB Network Partner AB Menu tree Appendix Version 1 0 00 1MRK 580 158 XEN Page 3 72 ...
Page 139: ...ABB Network Partner AB Terminal identification Version 1 0 00 1MRK 580 160 XEN Page 4 4 ...
Page 143: ...ABB Network Partner AB Activation of setting group Version 1 0 00 1MRK 580 162 XEN Page 4 8 ...
Page 175: ...ABB Network Partner AB Configurable logic Version 1 0 00 1MRK 580 161 XEN Page 4 40 ...
Page 385: ...ABB Network Partner AB Apparatus control Version 1 0 00 1MRK 580 150 XEN Page 6 100 ...
Page 495: ...ABB Network Partner AB Interlocking Version 1 0 00 1MRK 580 151 XEN Page 6 210 ...
Page 515: ...ABB Network Partner AB Event function Version 1 0 00 1MRK 580 140 XEN Page 6 230 ...
Page 519: ...ABB Network Partner AB Page IV ...
Page 561: ...ABB Network Partner AB Time synchronisation Version 1 0 00 1MRK 580 135 XEN Page 7 42 ...
Page 569: ...ABB Network Partner AB Internal events Version 1 0 00 1MRK 580 134 XEN Page 7 50 ...
Page 599: ...ABB Network Partner AB Index Version 1 0 01 1MRK 580 175 XEN Page 8 6 ...
Page 634: ......
Page 635: ......
Page 636: ......
Page 637: ......
Page 638: ......
Page 639: ......
Page 640: ......
Page 641: ......
Page 642: ......
Page 643: ......