ABB Network Partner AB
Auto-reclosing - Single- and/or
three-phase
Version 1.0-00
1MRK 580 170-XEN
Page 5
-
64
Another possibility is to set the output from the internal synchro-check
function to a permanently active signal. Set Operation = Release in the
synchro-check function. Then AR01-SYNC is configured to SYNC-
CHECKOK. See Fig. 6.
At confirmation from the synchro-check, or if the reclosing is of single-
phase type, the signal passes on.
At CBReady signal of the Close-Open (CO) type, it is checked that this
signal is present to allow for reclosing.
The synchronism and energizing check is allowed to be fulfilled for a cer-
tain time, tSync. If it does not, or if the other conditions are not fulfilled,
the reclosing is interrupted and blocked.
AR01-INHIBIT
Should this input signal appear, reclosing is inhibited. There is a tInhibit
reset timer, to ensure blocking during a few seconds after the signal is
removed. The input can, for example, be activated by a shunt reactor, or
by delayed back-up protection or breaker-failure protection.
Reclaim timer
This timer defines a period from the issue of a reclosing command, after
which the reclosing function is reset. Should a new tripping occur within
this time, it is treated as a continuation of the first fault.
When the signal to a closing command is given (Pulse AR), the reclaim
timer is started.
There is an AR State Control to track the actual state in the reclosing
sequence.
2.3.9 Pulsing of CB closing
command and
incrementing the
operation counters
• The AR01-CLOSECB, breaker closing command, is made as a pulse
of length, as set by the tPulse 0,1-1 s parameter.
• For breakers without an anti-pumping function, the closing pulse
cutting described below can be used. It is selected by means of the
CutPulse = On parameter. A new tripping pulse, (Trip Int.), then
interrupts the pulse. But the minimum length is always 50 ms.
• At the issue of a reclosing command, the associated reclosing opera-
tion counter is also incremented.
There is a counter for each type of reclosing and one for the total of
all reclosings. See Fig. 7.
2.3.10Transient fault
After the reclosing command, the reclaim timer keeps running for the set
time. If no tripping occurs within this time, tReclaim = 10 to 300 s, the
auto-reclosing function resets after the reclaim time. The breaker remains
closed and the operating gear recharges too, and AR01-CBCLOSED = 1,
AR01-CBREADY = 1.
Summary of Contents for REC 561
Page 19: ...ABB Network Partner AB Introduction REC 561 Version 1 0 00 1MRK 580 146 XEN Page 2 14 ...
Page 31: ...ABB Network Partner AB Requirements and basic technical data REC 561 Version 1 0 00 Page 2 26 ...
Page 49: ...ABB Network Partner AB Page IV ...
Page 121: ...ABB Network Partner AB Menu tree Appendix Version 1 0 00 1MRK 580 158 XEN Page 3 72 ...
Page 139: ...ABB Network Partner AB Terminal identification Version 1 0 00 1MRK 580 160 XEN Page 4 4 ...
Page 143: ...ABB Network Partner AB Activation of setting group Version 1 0 00 1MRK 580 162 XEN Page 4 8 ...
Page 175: ...ABB Network Partner AB Configurable logic Version 1 0 00 1MRK 580 161 XEN Page 4 40 ...
Page 385: ...ABB Network Partner AB Apparatus control Version 1 0 00 1MRK 580 150 XEN Page 6 100 ...
Page 495: ...ABB Network Partner AB Interlocking Version 1 0 00 1MRK 580 151 XEN Page 6 210 ...
Page 515: ...ABB Network Partner AB Event function Version 1 0 00 1MRK 580 140 XEN Page 6 230 ...
Page 519: ...ABB Network Partner AB Page IV ...
Page 561: ...ABB Network Partner AB Time synchronisation Version 1 0 00 1MRK 580 135 XEN Page 7 42 ...
Page 569: ...ABB Network Partner AB Internal events Version 1 0 00 1MRK 580 134 XEN Page 7 50 ...
Page 599: ...ABB Network Partner AB Index Version 1 0 01 1MRK 580 175 XEN Page 8 6 ...
Page 634: ......
Page 635: ......
Page 636: ......
Page 637: ......
Page 638: ......
Page 639: ......
Page 640: ......
Page 641: ......
Page 642: ......
Page 643: ......