ABB Network Partner AB
Measurement of alternating
quantities
Version 1.0-00
1MRK 580 159-XEN
Page 7
-
20
The last value reported (Y1 in Fig. 3) serves as a basic value for further
measurement. A difference is calculated between the last reported and the
newly measured value during new sample and is multiplied by the time
increment. These products are added until the pre-set value is exceeded.
The last measured value (Y2 in Fig. 3) is reported and set as a new base
for the following measurements.
Fig. 3
Integrating dead-band supervision
1.3.3 Periodic reporting
Users can select the periodic reporting of measured value in time intervals
between 1 and 3600 s. The measuring channel reports the value even if it
has not changed for more than the set limits of amplitude or integrating
dead-band supervision. To disable periodic reporting, set the reporting
time interval to 0 s.
1.3.4 Periodic reporting
with the dead-band
supervision in
parallel
The newly measured value is reported:
• After each time interval for the periodic reporting expired, or
• When the new value is detected by the dead-band supervision func-
tion
You can select the amplitude dead-band and the integrating dead-band.
You can set periodic reporting in time intervals between 1 and 3600 sec-
onds.
1.3.5 Periodic reporting
with the dead-band
supervision in series
Periodic reporting can operate serially with the dead-band supervision.
This means that the new value is reported only if the set time period
expired and if the dead-band limit was exceeded during the observed time.
The reporting of the new value depends on setting parameters for the
dead-band and for the periodic reporting. Table 1 presents the dependence
between different settings and the type of reporting for the new value of a
measured quantity.
1
2
3
4
5
6
Y1
Y2
Y3
reported values
Y
t
(x80159-3)
Summary of Contents for REC 561
Page 19: ...ABB Network Partner AB Introduction REC 561 Version 1 0 00 1MRK 580 146 XEN Page 2 14 ...
Page 31: ...ABB Network Partner AB Requirements and basic technical data REC 561 Version 1 0 00 Page 2 26 ...
Page 49: ...ABB Network Partner AB Page IV ...
Page 121: ...ABB Network Partner AB Menu tree Appendix Version 1 0 00 1MRK 580 158 XEN Page 3 72 ...
Page 139: ...ABB Network Partner AB Terminal identification Version 1 0 00 1MRK 580 160 XEN Page 4 4 ...
Page 143: ...ABB Network Partner AB Activation of setting group Version 1 0 00 1MRK 580 162 XEN Page 4 8 ...
Page 175: ...ABB Network Partner AB Configurable logic Version 1 0 00 1MRK 580 161 XEN Page 4 40 ...
Page 385: ...ABB Network Partner AB Apparatus control Version 1 0 00 1MRK 580 150 XEN Page 6 100 ...
Page 495: ...ABB Network Partner AB Interlocking Version 1 0 00 1MRK 580 151 XEN Page 6 210 ...
Page 515: ...ABB Network Partner AB Event function Version 1 0 00 1MRK 580 140 XEN Page 6 230 ...
Page 519: ...ABB Network Partner AB Page IV ...
Page 561: ...ABB Network Partner AB Time synchronisation Version 1 0 00 1MRK 580 135 XEN Page 7 42 ...
Page 569: ...ABB Network Partner AB Internal events Version 1 0 00 1MRK 580 134 XEN Page 7 50 ...
Page 599: ...ABB Network Partner AB Index Version 1 0 01 1MRK 580 175 XEN Page 8 6 ...
Page 634: ......
Page 635: ......
Page 636: ......
Page 637: ......
Page 638: ......
Page 639: ......
Page 640: ......
Page 641: ......
Page 642: ......
Page 643: ......