Disturbance report - Settings
ABB Network Partner AB
1MRK 580 133-XEN
Page
7 - 61
Version 1.0-00
3 Settings during test
3.1 Test mode
During testing, the operation of the Disturbance Report is required. The
setting of this operation is found at the MMI submenu:
Test
Test Mode
DisturbReport
Operation, DisturbSummary
When TestMode is set to On (Test/Mode/Operation = On), the setting of
the Disturbance Report parameters have the following impact:
Operation = Off
DisturbSummary = Off
• Disturbances are not stored.
• LED information is not shown on the MMI and not stored.
• No Disturbance Summary is scrolled on the MMI.
Operation = Off
DisturbSummary = On
• Disturbances are not stored.
• LED information (yellow - start, red - trip) are shown on the built-in
MMI, but not stored in the terminal.
• Disturbance summary is automatically scrolled on the built-in MMI
for the two latest registered disturbances, until cleared. The informa-
tion is not stored in the terminal.
Operation = On
DisturbSummary = Off or On
• The Disturbance Report works as in normal mode.
• Disturbances are stored. Data can be read from the built-in MMI, a
front-connected PC, or SMS.
• LED information (yellow - start, red - trip) is stored.
• Disturbance Summary is automatically scrolled on the built-in MMI
for the two latest registered disturbances, until cleared.
• All disturbance data stored during test mode remains in the terminal
when returning to normal mode.
3.2 Activation of manual
triggering
A Disturbance Report can be manually triggered from the built-in MMI, a
front-connected PC, or SMS. When the trig is activated, the manual trig
signal is generated. This feature is especially useful for testing.
Summary of Contents for REC 561
Page 19: ...ABB Network Partner AB Introduction REC 561 Version 1 0 00 1MRK 580 146 XEN Page 2 14 ...
Page 31: ...ABB Network Partner AB Requirements and basic technical data REC 561 Version 1 0 00 Page 2 26 ...
Page 49: ...ABB Network Partner AB Page IV ...
Page 121: ...ABB Network Partner AB Menu tree Appendix Version 1 0 00 1MRK 580 158 XEN Page 3 72 ...
Page 139: ...ABB Network Partner AB Terminal identification Version 1 0 00 1MRK 580 160 XEN Page 4 4 ...
Page 143: ...ABB Network Partner AB Activation of setting group Version 1 0 00 1MRK 580 162 XEN Page 4 8 ...
Page 175: ...ABB Network Partner AB Configurable logic Version 1 0 00 1MRK 580 161 XEN Page 4 40 ...
Page 385: ...ABB Network Partner AB Apparatus control Version 1 0 00 1MRK 580 150 XEN Page 6 100 ...
Page 495: ...ABB Network Partner AB Interlocking Version 1 0 00 1MRK 580 151 XEN Page 6 210 ...
Page 515: ...ABB Network Partner AB Event function Version 1 0 00 1MRK 580 140 XEN Page 6 230 ...
Page 519: ...ABB Network Partner AB Page IV ...
Page 561: ...ABB Network Partner AB Time synchronisation Version 1 0 00 1MRK 580 135 XEN Page 7 42 ...
Page 569: ...ABB Network Partner AB Internal events Version 1 0 00 1MRK 580 134 XEN Page 7 50 ...
Page 599: ...ABB Network Partner AB Index Version 1 0 01 1MRK 580 175 XEN Page 8 6 ...
Page 634: ......
Page 635: ......
Page 636: ......
Page 637: ......
Page 638: ......
Page 639: ......
Page 640: ......
Page 641: ......
Page 642: ......
Page 643: ......