Default configuration REC 561
ABB Network Partner AB
1MRK 580 188-XEN
Page
9 - 3
Version 1.0-00
• The binary output module of type BOM is defined as I/O module 2.
• No other types of I/O modules are defined.
• The interlocking module ABC_LINE is selected.
With the above choices, the tool automatically selects the BAYCONA
apparatus control module for the bay and SWICONB for the breaker and
SWICONC for other apparatuses. The interlocking module ABC_LINE is
also selected.
External fuse failure supervision is assumed, because no options are in
this default configuration.
2.2 Remote control
The REM worksheet consists of Single Command function blocks for
control of the included apparatuses from the gateway function connected
to the remote control centre. See also Apparatus Control (1MRK 580 150-
XEN).
2.3 Station MMI
The MMI worksheet contains function blocks for event handling of bay-
oriented signals, for example:
• If the bay is connected to the busbar
• Abnormal status
• Blocking of the whole bay
• Position of remote/station/local switch
Control signals for blocking the whole bay and for switching the bay in
station/remote are also displayed in this worksheet. Alarm signals for
external signals (via the binary input module), for example, external volt-
age fuse failure or synchro-check failure, and internal signals are con-
nected to the event function blocks for transferring to the station MMI
and/or remote gateway. There might be more internal signals, depending
on the options installed, for example, the A/D-conversion module.
If the time synchronization is performed by a minute pulse, the time syn-
chronization block must be connected to a binary input via an I/O module
block, see the I/O worksheet.
2.4 Communication with
other bays
In the COMM worksheet the sending and receiving part of the reservation
function between bays is displayed. The configuration is prepared to com-
municate with ten other bays including a bus-coupler bay. Normally, only
the bays, which influence the interlocking conditions, are reserved. Com-
plete the Multiple Command Function blocks for bay 2 to 10 with inter-
locking information from these bays in the same way as from the bus-
coupler bay. If there are no interlocking information to be used from bays
2 to 10, the Multiple Command Function blocks for these bays can be
deleted. For more information about the reservation principle see Appara-
tus Control (1MRK 580 150-XEN).
Summary of Contents for REC 561
Page 19: ...ABB Network Partner AB Introduction REC 561 Version 1 0 00 1MRK 580 146 XEN Page 2 14 ...
Page 31: ...ABB Network Partner AB Requirements and basic technical data REC 561 Version 1 0 00 Page 2 26 ...
Page 49: ...ABB Network Partner AB Page IV ...
Page 121: ...ABB Network Partner AB Menu tree Appendix Version 1 0 00 1MRK 580 158 XEN Page 3 72 ...
Page 139: ...ABB Network Partner AB Terminal identification Version 1 0 00 1MRK 580 160 XEN Page 4 4 ...
Page 143: ...ABB Network Partner AB Activation of setting group Version 1 0 00 1MRK 580 162 XEN Page 4 8 ...
Page 175: ...ABB Network Partner AB Configurable logic Version 1 0 00 1MRK 580 161 XEN Page 4 40 ...
Page 385: ...ABB Network Partner AB Apparatus control Version 1 0 00 1MRK 580 150 XEN Page 6 100 ...
Page 495: ...ABB Network Partner AB Interlocking Version 1 0 00 1MRK 580 151 XEN Page 6 210 ...
Page 515: ...ABB Network Partner AB Event function Version 1 0 00 1MRK 580 140 XEN Page 6 230 ...
Page 519: ...ABB Network Partner AB Page IV ...
Page 561: ...ABB Network Partner AB Time synchronisation Version 1 0 00 1MRK 580 135 XEN Page 7 42 ...
Page 569: ...ABB Network Partner AB Internal events Version 1 0 00 1MRK 580 134 XEN Page 7 50 ...
Page 599: ...ABB Network Partner AB Index Version 1 0 01 1MRK 580 175 XEN Page 8 6 ...
Page 634: ......
Page 635: ......
Page 636: ......
Page 637: ......
Page 638: ......
Page 639: ......
Page 640: ......
Page 641: ......
Page 642: ......
Page 643: ......