Interlocking
ABB Network Partner AB
1MRK 580 151-XEN
Page
6 - 197
Version 1.0-00
Table 8: Output signals for A1A2_BS
OUT:
DESCRIPTION:
IHxx-Q0OPREL
Opening of Q0 is allowed
IHxx-Q0OPITL
Opening of Q0 is forbidden
IHxx-Q0CLREL
Closing of Q0 is allowed
IHxx-Q0CLITL
Closing of Q0 is forbidden
IHxx-Q11REL
Switching of Q11 is allowed
IHxx-Q11ITL
Switching of Q11 is forbidden
IHxx-Q12REL
Switching of Q12 is allowed
IHxx-Q12ITL
Switching of Q12 is forbidden
IHxx-Q51REL
Switching of Q51 is allowed
IHxx-Q51ITL
Switching of Q51 is forbidden
IHxx-Q52REL
Switching of Q52 is allowed
IHxx-Q52ITL
Switching of Q52 is forbidden
IHxx-A1A2OPTR
No bus coupler connection between bus
section A1 and A2
IHxx-A1A2CLTR
Bus coupler connection between bus sec-
tion A1 and A2
IHxx-Q11OPTR
Signal is 1 if Q11 is open
IHxx-Q11CLTR
Signal is 1 if Q11 is closed
IHxx-Q12OPTR
Signal is 1 if Q12 is open
IHxx-Q12CLTR
Signal is 1 if Q12 is closed
IHxx-VPA1A2TR
Switch status of Q0, Q11 and Q12 are valid
(open or closed)
IHxx-VPQ11TR
Switch status of Q11 is valid (open or
closed)
IHxx-VPQ12TR
Switch status of Q12 is valid (open or
closed)
Summary of Contents for REC 561
Page 19: ...ABB Network Partner AB Introduction REC 561 Version 1 0 00 1MRK 580 146 XEN Page 2 14 ...
Page 31: ...ABB Network Partner AB Requirements and basic technical data REC 561 Version 1 0 00 Page 2 26 ...
Page 49: ...ABB Network Partner AB Page IV ...
Page 121: ...ABB Network Partner AB Menu tree Appendix Version 1 0 00 1MRK 580 158 XEN Page 3 72 ...
Page 139: ...ABB Network Partner AB Terminal identification Version 1 0 00 1MRK 580 160 XEN Page 4 4 ...
Page 143: ...ABB Network Partner AB Activation of setting group Version 1 0 00 1MRK 580 162 XEN Page 4 8 ...
Page 175: ...ABB Network Partner AB Configurable logic Version 1 0 00 1MRK 580 161 XEN Page 4 40 ...
Page 385: ...ABB Network Partner AB Apparatus control Version 1 0 00 1MRK 580 150 XEN Page 6 100 ...
Page 495: ...ABB Network Partner AB Interlocking Version 1 0 00 1MRK 580 151 XEN Page 6 210 ...
Page 515: ...ABB Network Partner AB Event function Version 1 0 00 1MRK 580 140 XEN Page 6 230 ...
Page 519: ...ABB Network Partner AB Page IV ...
Page 561: ...ABB Network Partner AB Time synchronisation Version 1 0 00 1MRK 580 135 XEN Page 7 42 ...
Page 569: ...ABB Network Partner AB Internal events Version 1 0 00 1MRK 580 134 XEN Page 7 50 ...
Page 599: ...ABB Network Partner AB Index Version 1 0 01 1MRK 580 175 XEN Page 8 6 ...
Page 634: ......
Page 635: ......
Page 636: ......
Page 637: ......
Page 638: ......
Page 639: ......
Page 640: ......
Page 641: ......
Page 642: ......
Page 643: ......