ABB Network Partner AB
Interlocking
Version 1.0-00
1MRK 580 151-XEN
Page 6
-
142
These signals from each double-breaker bay (DB_BUS) are needed:
Q1OPTR
Signal if Q1 is open.
Q2OPTR
Signal if Q2 is open.
VPQ1TR
The switch status of Q1 is valid.
VPQ2TR
The switch status of Q2 is valid.
EXDUP_DB
Signal if there is no transmission error from the bay that contains the
above information. This signal is taken from the data valid output on the
command function block.
These signals from each bus-section disconnector bay (A1A2_DC) are
also needed. For B1B2_DC, corresponding signals from busbar B are
used. The same type of module (A1A2_DC) is used for different busbars,
that is, for both bus-section disconnectors A1A2_DC and B1B2_DC.
DCOPTR
Signal if the bus-section disconnector is open.
VPDCTR
The switch status of A1A2_DC is valid.
EXDUP_DC
Signal if there is no transmission error from the bay that contains the
above information. This signal is taken from the data valid output on the
command function block.
The logic is identical to the double busbar configuration described in
“Signals in single breaker arrangement” on page 36.
4.2.8.3 Signals in breaker
and a half arrange-
ment
The busbar earthing switch is only allowed to operate if all disconnectors
of the bus section are open.
Fig. 41
Busbars divided by bus-section disconnectors (circuit break-
ers)
Section 1
Section 2
A1
B1
A2
B2
BH_LINE
BH_LINE
A1A2_DC(BS)
B1B2_DC(BS)
BB_ES
BB_ES
(X80151-41)
Summary of Contents for REC 561
Page 19: ...ABB Network Partner AB Introduction REC 561 Version 1 0 00 1MRK 580 146 XEN Page 2 14 ...
Page 31: ...ABB Network Partner AB Requirements and basic technical data REC 561 Version 1 0 00 Page 2 26 ...
Page 49: ...ABB Network Partner AB Page IV ...
Page 121: ...ABB Network Partner AB Menu tree Appendix Version 1 0 00 1MRK 580 158 XEN Page 3 72 ...
Page 139: ...ABB Network Partner AB Terminal identification Version 1 0 00 1MRK 580 160 XEN Page 4 4 ...
Page 143: ...ABB Network Partner AB Activation of setting group Version 1 0 00 1MRK 580 162 XEN Page 4 8 ...
Page 175: ...ABB Network Partner AB Configurable logic Version 1 0 00 1MRK 580 161 XEN Page 4 40 ...
Page 385: ...ABB Network Partner AB Apparatus control Version 1 0 00 1MRK 580 150 XEN Page 6 100 ...
Page 495: ...ABB Network Partner AB Interlocking Version 1 0 00 1MRK 580 151 XEN Page 6 210 ...
Page 515: ...ABB Network Partner AB Event function Version 1 0 00 1MRK 580 140 XEN Page 6 230 ...
Page 519: ...ABB Network Partner AB Page IV ...
Page 561: ...ABB Network Partner AB Time synchronisation Version 1 0 00 1MRK 580 135 XEN Page 7 42 ...
Page 569: ...ABB Network Partner AB Internal events Version 1 0 00 1MRK 580 134 XEN Page 7 50 ...
Page 599: ...ABB Network Partner AB Index Version 1 0 01 1MRK 580 175 XEN Page 8 6 ...
Page 634: ......
Page 635: ......
Page 636: ......
Page 637: ......
Page 638: ......
Page 639: ......
Page 640: ......
Page 641: ......
Page 642: ......
Page 643: ......