ABB Network Partner AB
Activation of setting group
Version 1.0-00
1MRK 580 162-XEN
Page 4
-
6
The voltage need not be permanently present on one binary input. Any
pulse, which must be longer than 200 ms activates the corresponding set-
ting group. The group remains active until some other command, issued
either through one of the binary inputs or by other means (built-in MMI,
SMS, SCS), activates another group.
Only one input can be active at the same time. This means that the con-
tact, which determines an actual active group, must open before the con-
tact that activates a new setting group closes.
Fig. 1
Connection of the function to external circuits
4 Testing
Configure the GRP--ACTGRPn input signals to the corresponding binary
inputs of a terminal and browse the built-in MMI for the information
about the active setting group under the menu:
Service Report
Active Group
Connect the appropriate dc voltage to the corresponding binary input of
the terminal and observe the information presented on the MMI unit. The
displayed information must always correspond to the activated input.
(X80162-1)
GRP--ACTGROUP1
GRP--ACTGROUP2
GRP--ACTGROUP3
GRP--ACTGROUP4
IOx-Bly1
IOx-Bly2
IOx-Bly3
IOx-Bly4
ACTIVE GROUP 1
ACTIVE GROUP 2
ACTIVE GROUP 4
ACTIVE GROUP 3
+RL2
Summary of Contents for REC 561
Page 19: ...ABB Network Partner AB Introduction REC 561 Version 1 0 00 1MRK 580 146 XEN Page 2 14 ...
Page 31: ...ABB Network Partner AB Requirements and basic technical data REC 561 Version 1 0 00 Page 2 26 ...
Page 49: ...ABB Network Partner AB Page IV ...
Page 121: ...ABB Network Partner AB Menu tree Appendix Version 1 0 00 1MRK 580 158 XEN Page 3 72 ...
Page 139: ...ABB Network Partner AB Terminal identification Version 1 0 00 1MRK 580 160 XEN Page 4 4 ...
Page 143: ...ABB Network Partner AB Activation of setting group Version 1 0 00 1MRK 580 162 XEN Page 4 8 ...
Page 175: ...ABB Network Partner AB Configurable logic Version 1 0 00 1MRK 580 161 XEN Page 4 40 ...
Page 385: ...ABB Network Partner AB Apparatus control Version 1 0 00 1MRK 580 150 XEN Page 6 100 ...
Page 495: ...ABB Network Partner AB Interlocking Version 1 0 00 1MRK 580 151 XEN Page 6 210 ...
Page 515: ...ABB Network Partner AB Event function Version 1 0 00 1MRK 580 140 XEN Page 6 230 ...
Page 519: ...ABB Network Partner AB Page IV ...
Page 561: ...ABB Network Partner AB Time synchronisation Version 1 0 00 1MRK 580 135 XEN Page 7 42 ...
Page 569: ...ABB Network Partner AB Internal events Version 1 0 00 1MRK 580 134 XEN Page 7 50 ...
Page 599: ...ABB Network Partner AB Index Version 1 0 01 1MRK 580 175 XEN Page 8 6 ...
Page 634: ......
Page 635: ......
Page 636: ......
Page 637: ......
Page 638: ......
Page 639: ......
Page 640: ......
Page 641: ......
Page 642: ......
Page 643: ......