SBxx-SY_RUN
Connected to the synchro-check module
(equipment). At true all timers in SWICONB
are stopped
SBxx-SY_FAIL
To be set to true when the synchro-check
fails and the command execution will stop
SBxx-AR_SEL
Selection input for fast autoreclosing. It is
used only with external selection relays
Table 18: Output signals for SWICONB
OUT:
DESCRIPTION:
SBxx-OX
Indication that the apparatus is in open posi-
tion. Result of the three single phase indica-
tions or blocking of the process updating or
by the manually entered open position
SBxx-CX
Indication that the apparatus is in close
position. Result of the three single phase
indications or blocking of the process updat-
ing or by the manually entered close posi-
tion
SBxx-POS_ERR
Position error. Result of that at least one of
following conditions are fulfilled: One phase
is both open and closed, one phase is in
middle position longer than T_POSERR, the
input POSIND_V is false
SBxx-POL_DISC
Output indicating pole discordance, after
that the time T_POL has elapsed
SBxx-MA_UPD_P
Output indicating manual control of position
updating
SBxx-SEL_OPEN
Selection output for open direction
SBxx-SEL_CLOS
Selection output for close direction
SBxx-EXE_OPEN
Execute output for open direction (settable
pulse length)
SBxx-EXE_CLOS
Execute output for close direction (settable
pulse length)
SBxx-SEL_RES
Reset the selection after successful or failed
operation (pulse output)
SBxx-SEL_ERR
Output indicating a failure in the selection, if
no feedback select signal FDB_SEL is acti-
vated before the time T_SEL has elapsed
SBxx-CMD_ERR
Output indicating a command error. That is
done if the position indication of the exe-
cuted apparatus does not indicate a start in
the position change before the time
T_START has elapsed
Table 17: Input signals for SWICONB
IN:
DESCRIPTION:
Summary of Contents for REC 561
Page 19: ...ABB Network Partner AB Introduction REC 561 Version 1 0 00 1MRK 580 146 XEN Page 2 14 ...
Page 31: ...ABB Network Partner AB Requirements and basic technical data REC 561 Version 1 0 00 Page 2 26 ...
Page 49: ...ABB Network Partner AB Page IV ...
Page 121: ...ABB Network Partner AB Menu tree Appendix Version 1 0 00 1MRK 580 158 XEN Page 3 72 ...
Page 139: ...ABB Network Partner AB Terminal identification Version 1 0 00 1MRK 580 160 XEN Page 4 4 ...
Page 143: ...ABB Network Partner AB Activation of setting group Version 1 0 00 1MRK 580 162 XEN Page 4 8 ...
Page 175: ...ABB Network Partner AB Configurable logic Version 1 0 00 1MRK 580 161 XEN Page 4 40 ...
Page 385: ...ABB Network Partner AB Apparatus control Version 1 0 00 1MRK 580 150 XEN Page 6 100 ...
Page 495: ...ABB Network Partner AB Interlocking Version 1 0 00 1MRK 580 151 XEN Page 6 210 ...
Page 515: ...ABB Network Partner AB Event function Version 1 0 00 1MRK 580 140 XEN Page 6 230 ...
Page 519: ...ABB Network Partner AB Page IV ...
Page 561: ...ABB Network Partner AB Time synchronisation Version 1 0 00 1MRK 580 135 XEN Page 7 42 ...
Page 569: ...ABB Network Partner AB Internal events Version 1 0 00 1MRK 580 134 XEN Page 7 50 ...
Page 599: ...ABB Network Partner AB Index Version 1 0 01 1MRK 580 175 XEN Page 8 6 ...
Page 634: ......
Page 635: ......
Page 636: ......
Page 637: ......
Page 638: ......
Page 639: ......
Page 640: ......
Page 641: ......
Page 642: ......
Page 643: ......