ABB Network Partner AB
Fuse-failure supervision function
Version 1.0-00
1MRK 580 169-XEN
Page 5
-
56
4.2 Signal list
4.3 Setting table
IN:
DESCRIPTION:
FUSE-MCB
Functional input sigal, which is normally connected via binary input to the auxiliary NC
contact of the miniature circut breaker in the voltage measuring circuits
FUSE-DISC
Functional input signal, which is normally connected via binary input to the auxiliary NC
contact of the line disconnector
OUT:
DESCRIPTION:
FUSE-VTSU
Output information on the operation of the FFS function. It is supposed to block all voltage
dependent functions within the terminal, except the distance protection. Configure it for
these purposes to the blocking inputs of the relevant functions.
FUSE-VTSZ
Output information on the operation of the FFS function. Its appearence is controlled by
the voltage/current check function. It should block the operation of distance protection
function during fuse-failure conditions in the voltage measuring circuits.
FUSE-VTF3PH
Output signal, which appears five seconds after the fuse-failure condition is detected if the
measured voltages in all three phases are low.
PARAMETER SETTING RANGE
DESCRIPTION
Operation
Off / Zeroseq / Nega-
tiveseq
Operating mode of the fuse-failure supervision function. The opera-
tion can be inhibited or based on measurement of the zero or negative
sequence quantities.
U>
(10-50)% of Ur/sqr(3)
The operating level of the voltage measuring element for the zero
sequence (3.U
0
) or negative sequence (3.U
2
) voltage, set as percent-
age of the terminal rated phase voltage.
I>
(10-50)% of Ir
The operating level of the current measuring element for the zero
sequence (3.I
0
) or negative sequence (3.I
2
) current, set as percentage
of the terminal rated current.
Summary of Contents for REC 561
Page 19: ...ABB Network Partner AB Introduction REC 561 Version 1 0 00 1MRK 580 146 XEN Page 2 14 ...
Page 31: ...ABB Network Partner AB Requirements and basic technical data REC 561 Version 1 0 00 Page 2 26 ...
Page 49: ...ABB Network Partner AB Page IV ...
Page 121: ...ABB Network Partner AB Menu tree Appendix Version 1 0 00 1MRK 580 158 XEN Page 3 72 ...
Page 139: ...ABB Network Partner AB Terminal identification Version 1 0 00 1MRK 580 160 XEN Page 4 4 ...
Page 143: ...ABB Network Partner AB Activation of setting group Version 1 0 00 1MRK 580 162 XEN Page 4 8 ...
Page 175: ...ABB Network Partner AB Configurable logic Version 1 0 00 1MRK 580 161 XEN Page 4 40 ...
Page 385: ...ABB Network Partner AB Apparatus control Version 1 0 00 1MRK 580 150 XEN Page 6 100 ...
Page 495: ...ABB Network Partner AB Interlocking Version 1 0 00 1MRK 580 151 XEN Page 6 210 ...
Page 515: ...ABB Network Partner AB Event function Version 1 0 00 1MRK 580 140 XEN Page 6 230 ...
Page 519: ...ABB Network Partner AB Page IV ...
Page 561: ...ABB Network Partner AB Time synchronisation Version 1 0 00 1MRK 580 135 XEN Page 7 42 ...
Page 569: ...ABB Network Partner AB Internal events Version 1 0 00 1MRK 580 134 XEN Page 7 50 ...
Page 599: ...ABB Network Partner AB Index Version 1 0 01 1MRK 580 175 XEN Page 8 6 ...
Page 634: ......
Page 635: ......
Page 636: ......
Page 637: ......
Page 638: ......
Page 639: ......
Page 640: ......
Page 641: ......
Page 642: ......
Page 643: ......