ABB Network Partner AB
Measurement of alternating
quantities
Version 1.0-00
1MRK 580 159-XEN
Page 7
-
30
HiAlarm
(0.0-9999.9)MW
Determines the operating value of the monitoring element which pro-
duces logical signal DA13-HIALARM
EnDeadB
Off, On
Enables (On) or disables (Off) the amplitude dead-band supervision
function
DeadBand
(0.0-9999.9)MW
Width of the amplitude dead-band within the ADBS function
EnIDeadB
Off, On
Enables (On) or disables (Off) the integrating dead-band supervision
function.
IDeadB
(0.0-9999.9)MW
Determines the width of the band within the IDBS function. Be aware of
the sampling frequency
EnDeadBP
Off, On
Enables (On) or disables (Off) the periodic dead-band reporting
Reactive power measuring channel
Operation
Off, On
Operation of the measuring channel enabled (On) or disabled (Off)
RepInt
(0-3600)Seconds
Duration of time interval between two reports at periodic reporting
function. Setting to 0 disables the periodic reporting.
EnAlarms
Off, On
Produces an immediate event at operation of any alarm monitoring ele-
ment, when On
EnAlRem
Off, On
Produces an immediate event at reset of any alarm monitoring element,
when On.
Hysteres
(0.0-9999.9)Mvar
Hysteresis for the set values of the monitoring elements in one measur-
ing channel.
LowAlarm
(0.0-9999.9)Mvar
Determines the operating value of the monitoring element which pro-
duces logical signal DA14-LOWALARM
LowWarn
(0.0-9999.9)Mvar
Determines the operating value of the monitoring element which pro-
duces logical signal DA14-LOWARN
HiWarn
(0.0-9999.9)Mvar
Determines the operating value of the monitoring element which pro-
duces logical signal DA14-HIWARN
HiAlarm
(0.0-9999.9)Mvar
Determines the operating value of the monitoring element which pro-
duces logical signal DA14-HIALARM
EnDeadB
Off, On
Enables (On) or disables (Off) the amplitude dead-band supervision
function
DeadBand
(0.0-9999.9)Mvar
Width of the amplitude dead-band within the ADBS function
EnIDeadB
Off, On
Enables (On) or disables (Off) the integrating dead-band supervision
function.
IDeadB
(0.0-9999.9)Mvar
Determines the width of the band within the IDBS function. Be aware of
the sampling frequency
EnDeadBP
Off, On
Enables (On) or disables (Off) the periodic dead-band reporting
PARAMETER:
SETTING RANGE: DESCRIPTION:
Summary of Contents for REC 561
Page 19: ...ABB Network Partner AB Introduction REC 561 Version 1 0 00 1MRK 580 146 XEN Page 2 14 ...
Page 31: ...ABB Network Partner AB Requirements and basic technical data REC 561 Version 1 0 00 Page 2 26 ...
Page 49: ...ABB Network Partner AB Page IV ...
Page 121: ...ABB Network Partner AB Menu tree Appendix Version 1 0 00 1MRK 580 158 XEN Page 3 72 ...
Page 139: ...ABB Network Partner AB Terminal identification Version 1 0 00 1MRK 580 160 XEN Page 4 4 ...
Page 143: ...ABB Network Partner AB Activation of setting group Version 1 0 00 1MRK 580 162 XEN Page 4 8 ...
Page 175: ...ABB Network Partner AB Configurable logic Version 1 0 00 1MRK 580 161 XEN Page 4 40 ...
Page 385: ...ABB Network Partner AB Apparatus control Version 1 0 00 1MRK 580 150 XEN Page 6 100 ...
Page 495: ...ABB Network Partner AB Interlocking Version 1 0 00 1MRK 580 151 XEN Page 6 210 ...
Page 515: ...ABB Network Partner AB Event function Version 1 0 00 1MRK 580 140 XEN Page 6 230 ...
Page 519: ...ABB Network Partner AB Page IV ...
Page 561: ...ABB Network Partner AB Time synchronisation Version 1 0 00 1MRK 580 135 XEN Page 7 42 ...
Page 569: ...ABB Network Partner AB Internal events Version 1 0 00 1MRK 580 134 XEN Page 7 50 ...
Page 599: ...ABB Network Partner AB Index Version 1 0 01 1MRK 580 175 XEN Page 8 6 ...
Page 634: ......
Page 635: ......
Page 636: ......
Page 637: ......
Page 638: ......
Page 639: ......
Page 640: ......
Page 641: ......
Page 642: ......
Page 643: ......