4.2.12Automatic functions
Using the same methods as for ordinary commands that come from differ-
ent operator places, there are inputs (select/execute/cancel) to be con-
nected from other application programs in the form of automatic
functions. These programs can be located in the same REC 561, in
another terminal, or in a station computer.
One usage for automatic programs is when the apparatuses are included in
a sequence, for example, a busbar transfer.
Fig. 35 shows the signals connected to the COMCON module.
Fig. 35
Connections to automatic functions
4.2.13Command output
module
The command outputs from the apparatus control modules can be con-
nected to the output module in different ways depending on functionality.
The output module has supervised outputs. That is, the output relays are
continuously supervised in a way that an unwanted activation is detected,
which stops the continuation of the operation. This is performed by using
the ERROR signal connected to BLKCONL for blocking the command.
To get a secure command, two contacts are connected in serial. The fol-
COMCON
AU_SEL_O
AU_SEL_C
AU_OPEN
AU_CLOSE
AU_CANC
SEL_SEQ
For example, outputs from
AU_MODE
SEQ_STA
.
.
.
To sequence
program or/and
the station MMI
a sequence program
(X80150-35)
Summary of Contents for REC 561
Page 19: ...ABB Network Partner AB Introduction REC 561 Version 1 0 00 1MRK 580 146 XEN Page 2 14 ...
Page 31: ...ABB Network Partner AB Requirements and basic technical data REC 561 Version 1 0 00 Page 2 26 ...
Page 49: ...ABB Network Partner AB Page IV ...
Page 121: ...ABB Network Partner AB Menu tree Appendix Version 1 0 00 1MRK 580 158 XEN Page 3 72 ...
Page 139: ...ABB Network Partner AB Terminal identification Version 1 0 00 1MRK 580 160 XEN Page 4 4 ...
Page 143: ...ABB Network Partner AB Activation of setting group Version 1 0 00 1MRK 580 162 XEN Page 4 8 ...
Page 175: ...ABB Network Partner AB Configurable logic Version 1 0 00 1MRK 580 161 XEN Page 4 40 ...
Page 385: ...ABB Network Partner AB Apparatus control Version 1 0 00 1MRK 580 150 XEN Page 6 100 ...
Page 495: ...ABB Network Partner AB Interlocking Version 1 0 00 1MRK 580 151 XEN Page 6 210 ...
Page 515: ...ABB Network Partner AB Event function Version 1 0 00 1MRK 580 140 XEN Page 6 230 ...
Page 519: ...ABB Network Partner AB Page IV ...
Page 561: ...ABB Network Partner AB Time synchronisation Version 1 0 00 1MRK 580 135 XEN Page 7 42 ...
Page 569: ...ABB Network Partner AB Internal events Version 1 0 00 1MRK 580 134 XEN Page 7 50 ...
Page 599: ...ABB Network Partner AB Index Version 1 0 01 1MRK 580 175 XEN Page 8 6 ...
Page 634: ......
Page 635: ......
Page 636: ......
Page 637: ......
Page 638: ......
Page 639: ......
Page 640: ......
Page 641: ......
Page 642: ......
Page 643: ......