Interlocking
ABB Network Partner AB
1MRK 580 151-XEN
Page
6 - 137
Version 1.0-00
To derive the signals:
ABCDC_OP
Signal if all disconnectors of this busbar section are open.
VP_ABCDC
The switch status of ABCDC is valid.
EXDUP_BB
Signal if no transmission error from any bay containing the above infor-
mation.
These signals from each line bay (ABC_LINE), each transformer bay
(AB_TRAFO), and each bus-coupler bay (ABC_BC) are needed:
Q1OPTR
Signal if Q1 is open.
Q2OPTR
Signal if Q2 (AB_TRAFO, ABC_LINE) is open.
Q20OPTR
Signal if Q2 and Q20 (ABC_BC) are open.
Q7OPTR
Signal if Q7 is open.
VPQ1TR
The switch status of Q1 is valid.
VPQ2TR
The switch status of Q2 is valid.
VPQ20TR
The switch status of Q2 and Q20 are valid.
VPQ7TR
The switch status of Q7 is valid.
EXDUP_BB
Signal if there is no transmission error from the bay that contains the
above information.This signal is taken from the data valid output on the
command function block.
These signals from each bus-section disconnector bay (A1A2_DC) are
also needed. For B1B2_DC, corresponding signals from busbar B are
used. The same type of module (A1A2_DC) is used for different busbars,
that is, for both bus-section disconnectors A1A2_DC and B1B2_DC.
DCOPTR
Signal if the bus-section disconnector is open.
VPDCTR
The switch status of A1A2_DC is valid.
Summary of Contents for REC 561
Page 19: ...ABB Network Partner AB Introduction REC 561 Version 1 0 00 1MRK 580 146 XEN Page 2 14 ...
Page 31: ...ABB Network Partner AB Requirements and basic technical data REC 561 Version 1 0 00 Page 2 26 ...
Page 49: ...ABB Network Partner AB Page IV ...
Page 121: ...ABB Network Partner AB Menu tree Appendix Version 1 0 00 1MRK 580 158 XEN Page 3 72 ...
Page 139: ...ABB Network Partner AB Terminal identification Version 1 0 00 1MRK 580 160 XEN Page 4 4 ...
Page 143: ...ABB Network Partner AB Activation of setting group Version 1 0 00 1MRK 580 162 XEN Page 4 8 ...
Page 175: ...ABB Network Partner AB Configurable logic Version 1 0 00 1MRK 580 161 XEN Page 4 40 ...
Page 385: ...ABB Network Partner AB Apparatus control Version 1 0 00 1MRK 580 150 XEN Page 6 100 ...
Page 495: ...ABB Network Partner AB Interlocking Version 1 0 00 1MRK 580 151 XEN Page 6 210 ...
Page 515: ...ABB Network Partner AB Event function Version 1 0 00 1MRK 580 140 XEN Page 6 230 ...
Page 519: ...ABB Network Partner AB Page IV ...
Page 561: ...ABB Network Partner AB Time synchronisation Version 1 0 00 1MRK 580 135 XEN Page 7 42 ...
Page 569: ...ABB Network Partner AB Internal events Version 1 0 00 1MRK 580 134 XEN Page 7 50 ...
Page 599: ...ABB Network Partner AB Index Version 1 0 01 1MRK 580 175 XEN Page 8 6 ...
Page 634: ......
Page 635: ......
Page 636: ......
Page 637: ......
Page 638: ......
Page 639: ......
Page 640: ......
Page 641: ......
Page 642: ......
Page 643: ......