ABB Network Partner AB
Apparatus control
Version 1.0-00
1MRK 580 150-XEN
Page 6
-
26
Fig. 13 shows an overview of a disconnector/earthing switch module.
Fig. 13
Overview of a disconnector/earthing switch configuration
4.2 Connections to other
functions
4.2.1 Reservation function
The reservation function is primarily a method to transfer interlocking
information from other bays in a safe way.
To reserve other bays, the BAYCON bay control module needs interac-
tion with the bays that must be reserved. Note that only bays that must be
reserved or need to reserve other bays must have these connections.
The question of which bays that should be reserved by this bay is delivery
specific. In general there are three ways:
• Only the bays that influence the interlocking conditions must be
reserved.
• The whole voltage level must be reserved. All other bays on this bus-
bar voltage level must be blocked.
• The whole station must be reserved. All other bays in the station
must be blocked.
The connections to reserve the apparatuses within the own bay are shown
in Fig. 14. The timing diagram is shown in Fig. 15. The reservation func-
tion follows the steps below:
1. The op_SEL_O selection signal or op_SEL_C selection signal
(op=operator place R/S/L) in COMCON is activated when an apparatus
is selected for operation. COMCON sets the RQ_SEL output.
2. The signal RQ_SEL activates the RE_BAYS output via RQ_SELx in
BAYCON for reserving other bays. After successful acknowledgement
from other bays, the select output (SELx) is set to inform other ele-
ments that it has reached a reserved state. In this state, it will not accept
other requests, which ensures that no other operations are possible in
this bay.
COMCON
SWICONC
BI/BO
Operator
Open
Close
command
Interlocking
INT_LOCK
(X80150-13)
Summary of Contents for REC 561
Page 19: ...ABB Network Partner AB Introduction REC 561 Version 1 0 00 1MRK 580 146 XEN Page 2 14 ...
Page 31: ...ABB Network Partner AB Requirements and basic technical data REC 561 Version 1 0 00 Page 2 26 ...
Page 49: ...ABB Network Partner AB Page IV ...
Page 121: ...ABB Network Partner AB Menu tree Appendix Version 1 0 00 1MRK 580 158 XEN Page 3 72 ...
Page 139: ...ABB Network Partner AB Terminal identification Version 1 0 00 1MRK 580 160 XEN Page 4 4 ...
Page 143: ...ABB Network Partner AB Activation of setting group Version 1 0 00 1MRK 580 162 XEN Page 4 8 ...
Page 175: ...ABB Network Partner AB Configurable logic Version 1 0 00 1MRK 580 161 XEN Page 4 40 ...
Page 385: ...ABB Network Partner AB Apparatus control Version 1 0 00 1MRK 580 150 XEN Page 6 100 ...
Page 495: ...ABB Network Partner AB Interlocking Version 1 0 00 1MRK 580 151 XEN Page 6 210 ...
Page 515: ...ABB Network Partner AB Event function Version 1 0 00 1MRK 580 140 XEN Page 6 230 ...
Page 519: ...ABB Network Partner AB Page IV ...
Page 561: ...ABB Network Partner AB Time synchronisation Version 1 0 00 1MRK 580 135 XEN Page 7 42 ...
Page 569: ...ABB Network Partner AB Internal events Version 1 0 00 1MRK 580 134 XEN Page 7 50 ...
Page 599: ...ABB Network Partner AB Index Version 1 0 01 1MRK 580 175 XEN Page 8 6 ...
Page 634: ......
Page 635: ......
Page 636: ......
Page 637: ......
Page 638: ......
Page 639: ......
Page 640: ......
Page 641: ......
Page 642: ......
Page 643: ......