The same type of module (A1A2_DC) is used for different busbars, that
is, for both bus-section disconnector A1A2_DC and B1B2_DC. But for
B1B2_DC, corresponding signals from busbar B are used.
Fig. 33
Busbars divided by bus-section disconnectors (circuit break-
ers)
The project-specific logic are the same as for the logic for the double-
breaker configuration. See “Signals in double-breaker arrangement” on
page 132.
A1DC_OP
Signal if all disconnectors on busbar A1 are open.
A2DC_OP
Signal if all disconnectors on busbar A2 are open.
VPA1_DC
The switch status of A1_DC is valid.
VPA2_DC
The switch status of A2_DC is valid.
EXDUP_BB
Signal if there is no transmission error from bay BH (breaker and a half)
that contains the above information.
4.2.8 Bus earthing switch
4.2.8.1 Signals in single
breaker arrangement
The busbar earthing switch is only allowed to operate if all disconnectors
of the bus section are open.
Fig. 34
Busbars divided by bus-section disconnectors (circuit breakers)
Section 1
Section 2
A1
B1
A2
B2
BH_LINE BH_LINE
BH_LINE BH_LINE
A1A2_DC(BS)
B1B2_DC(BS)
(X80151-33)
Section 1
Section 2
A1
B1
C
A2
B2
C
ABC_LINE
ABC_BC
ABC_LINE
A1A2_DC(BS)
B1B2_DC(BS)
AB_TRAFO
BB_ES
BB_ES
(X80151-34)
Summary of Contents for REC 561
Page 19: ...ABB Network Partner AB Introduction REC 561 Version 1 0 00 1MRK 580 146 XEN Page 2 14 ...
Page 31: ...ABB Network Partner AB Requirements and basic technical data REC 561 Version 1 0 00 Page 2 26 ...
Page 49: ...ABB Network Partner AB Page IV ...
Page 121: ...ABB Network Partner AB Menu tree Appendix Version 1 0 00 1MRK 580 158 XEN Page 3 72 ...
Page 139: ...ABB Network Partner AB Terminal identification Version 1 0 00 1MRK 580 160 XEN Page 4 4 ...
Page 143: ...ABB Network Partner AB Activation of setting group Version 1 0 00 1MRK 580 162 XEN Page 4 8 ...
Page 175: ...ABB Network Partner AB Configurable logic Version 1 0 00 1MRK 580 161 XEN Page 4 40 ...
Page 385: ...ABB Network Partner AB Apparatus control Version 1 0 00 1MRK 580 150 XEN Page 6 100 ...
Page 495: ...ABB Network Partner AB Interlocking Version 1 0 00 1MRK 580 151 XEN Page 6 210 ...
Page 515: ...ABB Network Partner AB Event function Version 1 0 00 1MRK 580 140 XEN Page 6 230 ...
Page 519: ...ABB Network Partner AB Page IV ...
Page 561: ...ABB Network Partner AB Time synchronisation Version 1 0 00 1MRK 580 135 XEN Page 7 42 ...
Page 569: ...ABB Network Partner AB Internal events Version 1 0 00 1MRK 580 134 XEN Page 7 50 ...
Page 599: ...ABB Network Partner AB Index Version 1 0 01 1MRK 580 175 XEN Page 8 6 ...
Page 634: ......
Page 635: ......
Page 636: ......
Page 637: ......
Page 638: ......
Page 639: ......
Page 640: ......
Page 641: ......
Page 642: ......
Page 643: ......