ABB Network Partner AB
Apparatus control
Version 1.0-00
1MRK 580 150-XEN
Page 6
-
24
When operating apparatus 1, the general procedure is as follow:
1. Command to set valid operator place for the complete bay. This com-
mand can come from station MMI or the local back-up panel. The
command is given when there is need to change the operator place
only.
2. COMCON receives commands to operate the apparatus. Only com-
mands from the valid operator place are accepted. The first command
is a request to select the apparatus.
3. The BAYCON element receives the request from COMCON.
4. The BAYCON element sends a signal to other control programs to
reserve their bays (if necessary). That is, no operation is allowed there.
Acknowledgement signals should be received.
Other control programs can be placed in the same REC 561 or in other
REC 561s (bay-bay communication).
5. If everything is OK, the select signal is passed through to the SWICON
element and is displayed on the station MMI.
6. The program is now prepared to receive the execute command from the
operator.
7. The closing or opening command is sent to the selected apparatus.
Different kinds of errors can be detected.
Operator related errors, if too long time between:
• The select and the execute commands
• A request to override (reservation and/or interlocking) and the fol-
lowing select command
Apparatus-related errors, if too long time between:
• The apparatus starts to move
• The apparatus reaches the new position
Other apparatus-related errors:
• Pole discordance
• Command error (for example, when the apparatus is blocked or
interlocked)
Other errors:
• Reservation failure
• Binary output board error
Summary of Contents for REC 561
Page 19: ...ABB Network Partner AB Introduction REC 561 Version 1 0 00 1MRK 580 146 XEN Page 2 14 ...
Page 31: ...ABB Network Partner AB Requirements and basic technical data REC 561 Version 1 0 00 Page 2 26 ...
Page 49: ...ABB Network Partner AB Page IV ...
Page 121: ...ABB Network Partner AB Menu tree Appendix Version 1 0 00 1MRK 580 158 XEN Page 3 72 ...
Page 139: ...ABB Network Partner AB Terminal identification Version 1 0 00 1MRK 580 160 XEN Page 4 4 ...
Page 143: ...ABB Network Partner AB Activation of setting group Version 1 0 00 1MRK 580 162 XEN Page 4 8 ...
Page 175: ...ABB Network Partner AB Configurable logic Version 1 0 00 1MRK 580 161 XEN Page 4 40 ...
Page 385: ...ABB Network Partner AB Apparatus control Version 1 0 00 1MRK 580 150 XEN Page 6 100 ...
Page 495: ...ABB Network Partner AB Interlocking Version 1 0 00 1MRK 580 151 XEN Page 6 210 ...
Page 515: ...ABB Network Partner AB Event function Version 1 0 00 1MRK 580 140 XEN Page 6 230 ...
Page 519: ...ABB Network Partner AB Page IV ...
Page 561: ...ABB Network Partner AB Time synchronisation Version 1 0 00 1MRK 580 135 XEN Page 7 42 ...
Page 569: ...ABB Network Partner AB Internal events Version 1 0 00 1MRK 580 134 XEN Page 7 50 ...
Page 599: ...ABB Network Partner AB Index Version 1 0 01 1MRK 580 175 XEN Page 8 6 ...
Page 634: ......
Page 635: ......
Page 636: ......
Page 637: ......
Page 638: ......
Page 639: ......
Page 640: ......
Page 641: ......
Page 642: ......
Page 643: ......