Breaker-failure protection
ABB Network Partner AB
1MRK 580 171-XEN
Page
5 - 85
Version 1.0-00
2 Theory of operation
The breaker-failure protection starts on a single-phase or three-phase con-
dition, either from an external protection, or internally from a protection
trip signal in the terminal.
The breaker receiving the original protection trip command can be
retripped from the BFP. The retrip can be controlled by a current check, or
carried out as a direct retrip without any current check. The direct retrip
can be used without inconvenience, because the breaker-to-trip has
already received a tripping command, and the direct retrip does not cause
any unselective tripping
The use of retrip limits the extent of unwanted power disconnection in
case of an accidental start of the BFP at work in the initiating circuitry,
with the primary circuit in service and the load above the set current level.
The back-up trip is sent to the adjacent circuit breaker to clear the fault
and disconnect the failing circuit breaker.
Fig. 3
Logic diagram of breaker-failure protection, phase L1
(X80171-3)
t
t1
&
t
t
t1
t
t2
&
IL1
START L1
L1
ASD
RMS
RET1
RET0
RET2
BUTL1
RTL1
RET0: No retrip
RET1: Retrip with current check
RET2: Unconditional retrip
RET1:
Summary of Contents for REC 561
Page 19: ...ABB Network Partner AB Introduction REC 561 Version 1 0 00 1MRK 580 146 XEN Page 2 14 ...
Page 31: ...ABB Network Partner AB Requirements and basic technical data REC 561 Version 1 0 00 Page 2 26 ...
Page 49: ...ABB Network Partner AB Page IV ...
Page 121: ...ABB Network Partner AB Menu tree Appendix Version 1 0 00 1MRK 580 158 XEN Page 3 72 ...
Page 139: ...ABB Network Partner AB Terminal identification Version 1 0 00 1MRK 580 160 XEN Page 4 4 ...
Page 143: ...ABB Network Partner AB Activation of setting group Version 1 0 00 1MRK 580 162 XEN Page 4 8 ...
Page 175: ...ABB Network Partner AB Configurable logic Version 1 0 00 1MRK 580 161 XEN Page 4 40 ...
Page 385: ...ABB Network Partner AB Apparatus control Version 1 0 00 1MRK 580 150 XEN Page 6 100 ...
Page 495: ...ABB Network Partner AB Interlocking Version 1 0 00 1MRK 580 151 XEN Page 6 210 ...
Page 515: ...ABB Network Partner AB Event function Version 1 0 00 1MRK 580 140 XEN Page 6 230 ...
Page 519: ...ABB Network Partner AB Page IV ...
Page 561: ...ABB Network Partner AB Time synchronisation Version 1 0 00 1MRK 580 135 XEN Page 7 42 ...
Page 569: ...ABB Network Partner AB Internal events Version 1 0 00 1MRK 580 134 XEN Page 7 50 ...
Page 599: ...ABB Network Partner AB Index Version 1 0 01 1MRK 580 175 XEN Page 8 6 ...
Page 634: ......
Page 635: ......
Page 636: ......
Page 637: ......
Page 638: ......
Page 639: ......
Page 640: ......
Page 641: ......
Page 642: ......
Page 643: ......