Loss of power system voltage
Version 1.0-00
1MRK 580 153-XEN
Page 5
-
98
The LOV--TRIP output signal should be configured to the corre-
sponding binary output (relay contact) under the submenu
Configuration
Slotnn-ZZZy
Where nn is the corresponding number of the I/O module, and y is
the number of the output on the module. ZZZ indicates the type of
I/O modulethat is installed in the terminal. Connect the indication
instrument to the relevant output terminals.
1.3
Set the operation of the fuse failure function to off mode under the
sub menu:
Settings
Functions
Group n
FuseFailure
1.4
Simultaneously increase the measured three-phase voltages for at
least 10 seconds to their rated value and consider the correct phase
relations between them. The LOV--TRIP signal should not appear
on the output terminal after a time period longer than seven sec-
onds.
1.5
Simultaneously disconnect the voltage in all three phases and note
the LOV--TRIP signal. It should appear approximately seven sec-
onds after the voltage has been switched off. Its duration should be
about 150 ms.
1.6
Simultaneously increase the measured voltages to their rated values
and decrease them again to zero within an interval shorter than
threeseconds. No LOV--TRIP signal should appear.
1.7
Increase the measured voltages to their rated values for at least 10
seconds. Disconnect one phase and, after a time longer than 10 sec-
onds, also the remaining two phases. No LOV--TRIP signal should
appear after a time period longer than seven seconds.
1.8
Increase the measured voltages to their rated values for at least 10
seconds. Connect a nominal DC voltage to the binary input LOV--
BC. Simultaneously disconnect all three voltages from the terminal.
No LOV--TRIP signal should appear after a time period longer than
seven seconds.
1.9
Disconnect the DC voltage from the LOV--BC binary input.
1.10 Set the operation of the fuse-failure supervision function (if built
into the terminal) to On mode. Increase the measured voltages and
all three phase currents to their rated values for at least 10 seconds.
Disconnect the voltage in one phase and about a half a second later,
also in the remaining two phases. No LOV--TRIP signal should
appear.
Summary of Contents for REC 561
Page 19: ...ABB Network Partner AB Introduction REC 561 Version 1 0 00 1MRK 580 146 XEN Page 2 14 ...
Page 31: ...ABB Network Partner AB Requirements and basic technical data REC 561 Version 1 0 00 Page 2 26 ...
Page 49: ...ABB Network Partner AB Page IV ...
Page 121: ...ABB Network Partner AB Menu tree Appendix Version 1 0 00 1MRK 580 158 XEN Page 3 72 ...
Page 139: ...ABB Network Partner AB Terminal identification Version 1 0 00 1MRK 580 160 XEN Page 4 4 ...
Page 143: ...ABB Network Partner AB Activation of setting group Version 1 0 00 1MRK 580 162 XEN Page 4 8 ...
Page 175: ...ABB Network Partner AB Configurable logic Version 1 0 00 1MRK 580 161 XEN Page 4 40 ...
Page 385: ...ABB Network Partner AB Apparatus control Version 1 0 00 1MRK 580 150 XEN Page 6 100 ...
Page 495: ...ABB Network Partner AB Interlocking Version 1 0 00 1MRK 580 151 XEN Page 6 210 ...
Page 515: ...ABB Network Partner AB Event function Version 1 0 00 1MRK 580 140 XEN Page 6 230 ...
Page 519: ...ABB Network Partner AB Page IV ...
Page 561: ...ABB Network Partner AB Time synchronisation Version 1 0 00 1MRK 580 135 XEN Page 7 42 ...
Page 569: ...ABB Network Partner AB Internal events Version 1 0 00 1MRK 580 134 XEN Page 7 50 ...
Page 599: ...ABB Network Partner AB Index Version 1 0 01 1MRK 580 175 XEN Page 8 6 ...
Page 634: ......
Page 635: ......
Page 636: ......
Page 637: ......
Page 638: ......
Page 639: ......
Page 640: ......
Page 641: ......
Page 642: ......
Page 643: ......