ABB Network Partner AB
Measurement of alternating
quantities
Version 1.0-00
1MRK 580 159-XEN
Page 7
-
32
EventMask I3
No Events, Report
Events
Enables (Report Events) or disables (No Events) reporting of events
from channel DA08 to the SCS
EventMask I2
No Events, Report
Events
Enables (Report Events) or disables (No Events) reporting of events
from channel DA07 to the SCS
EventMask I1
No Events, Report
Events
Enables (Report Events) or disables (No Events) reporting of events
from channel DA06 to the SCS
EventMask U5
No Events, Report
Events
Enables (Report Events) or disables (No Events) reporting of events
from channel DA05 to the SCS
EventMask U4
No Events, Report
Events
Enables (Report Events) or disables (No Events) reporting of events
from channel DA04 to the SCS
EventMask U3
No Events, Report
Events
Enables (Report Events) or disables (No Events) reporting of events
from channel DA03 to the SCS
EventMask U2
No Events, Report
Events
Enables (Report Events) or disables (No Events) reporting of events
from channel DA02 to the SCS
EventMask U1
No Events, Report
Events
Enables (Report Events) or disables (No Events) reporting of events
from channel DA01 to the SCS
The following parameters are settable under the Configuration-
AnalogInputs submenu. Settings are possible also by means of the
MMI module
Name
13 character name
Name of the analogue measuring channel.Enter up to 13 characters for
the name of measured quantity. the name appears automatically in dis-
turbance evaluation program REVAL. The default names are:
U1,..,U5,I1,..I5,U,I,P,Q,f
VTPrim
(1-9999) kV
Rated primary voltage of the voltage instrument transformer connected
to the Un (n = 1 to 5) measuring channel
CTPrim
(1-9999) A
Rated primary current of the current instrument transformer connected
to the In (n = 1 to 5) measuring channel
PARAMETER:
SETTING RANGE: DESCRIPTION:
Summary of Contents for REC 561
Page 19: ...ABB Network Partner AB Introduction REC 561 Version 1 0 00 1MRK 580 146 XEN Page 2 14 ...
Page 31: ...ABB Network Partner AB Requirements and basic technical data REC 561 Version 1 0 00 Page 2 26 ...
Page 49: ...ABB Network Partner AB Page IV ...
Page 121: ...ABB Network Partner AB Menu tree Appendix Version 1 0 00 1MRK 580 158 XEN Page 3 72 ...
Page 139: ...ABB Network Partner AB Terminal identification Version 1 0 00 1MRK 580 160 XEN Page 4 4 ...
Page 143: ...ABB Network Partner AB Activation of setting group Version 1 0 00 1MRK 580 162 XEN Page 4 8 ...
Page 175: ...ABB Network Partner AB Configurable logic Version 1 0 00 1MRK 580 161 XEN Page 4 40 ...
Page 385: ...ABB Network Partner AB Apparatus control Version 1 0 00 1MRK 580 150 XEN Page 6 100 ...
Page 495: ...ABB Network Partner AB Interlocking Version 1 0 00 1MRK 580 151 XEN Page 6 210 ...
Page 515: ...ABB Network Partner AB Event function Version 1 0 00 1MRK 580 140 XEN Page 6 230 ...
Page 519: ...ABB Network Partner AB Page IV ...
Page 561: ...ABB Network Partner AB Time synchronisation Version 1 0 00 1MRK 580 135 XEN Page 7 42 ...
Page 569: ...ABB Network Partner AB Internal events Version 1 0 00 1MRK 580 134 XEN Page 7 50 ...
Page 599: ...ABB Network Partner AB Index Version 1 0 01 1MRK 580 175 XEN Page 8 6 ...
Page 634: ......
Page 635: ......
Page 636: ......
Page 637: ......
Page 638: ......
Page 639: ......
Page 640: ......
Page 641: ......
Page 642: ......
Page 643: ......