ABB Network Partner AB
Auto-reclosing - Single- and/or
three-phase
Version 1.0-00
1MRK 580 170-XEN
Page 5
-
60
AR01-SYNC
Synchro-check OK from the internal synchro-
check function or an external device required for
three-phase auto-reclosing.
AR01-PLCLOST
Power line carrier or other form of permissive sig-
nal lost. An optional input signal at loss of a com-
munication channel in a permissive line protection
scheme. Can extend the AR open time.
AR01-TRSOTF
Protection trip switch-onto-fault.
AR01-TPTRIP
Three-phase trip. Signal to the auto-reclosing func-
tion that a three-phase tripping occurred.
AR01-WAIT
Signal to the low priority auto-reclosing function
from the master in multi-breaker arrangements for
sequential reclosing.
Output signals:
AR01-SETON
Indicates that the AR operation is On, that is, opera-
tive.
AR01-READY
Indicates that the AR function is ready for a new
AR cycle. It is On and it is not started or blocked.
AR01-INPROGR
Auto-reclosing in progress. Activated during the
AR open time.
AR01-SP1
Auto-reclosing single-phase, Shot 1 in progress.
AR01-TP1
Auto-reclosing three-phase, Shot 1 in progress.
AR01-TP2
Auto-reclosing three-phase, Shot 2 in progress.
AR01-UNSUC
Auto-reclosing unsuccessful. Activated at a new
trip after the last programmed shot.
AR01-CLOSECB
Close circuit-breaker command.
AR01-P3PH
Prepare three-phase trip. Control of the next trip
operation.
AR01-P1PH
Permit single-phase trip. Inverse signal to AR01-P3PH.
AR01-WFMASTER Wait from master. Issued by the high priority unit
for sequential reclosing.
AR01-LONGDURA Output signal inhibiting the auto-reclosing when
the extension of AR OPEN TIME is set off.
2.2 AR Operation
You can control the auto-reclosing function from the MMI. Use the Operation
parameter, which you can set to Off, Stand by or On. See Fig. 3.
Off deactivates the Operation parameter. On activates automatic reclos-
ing. Stand by enables On and Off Operation via input signal pulses.
Summary of Contents for REC 561
Page 19: ...ABB Network Partner AB Introduction REC 561 Version 1 0 00 1MRK 580 146 XEN Page 2 14 ...
Page 31: ...ABB Network Partner AB Requirements and basic technical data REC 561 Version 1 0 00 Page 2 26 ...
Page 49: ...ABB Network Partner AB Page IV ...
Page 121: ...ABB Network Partner AB Menu tree Appendix Version 1 0 00 1MRK 580 158 XEN Page 3 72 ...
Page 139: ...ABB Network Partner AB Terminal identification Version 1 0 00 1MRK 580 160 XEN Page 4 4 ...
Page 143: ...ABB Network Partner AB Activation of setting group Version 1 0 00 1MRK 580 162 XEN Page 4 8 ...
Page 175: ...ABB Network Partner AB Configurable logic Version 1 0 00 1MRK 580 161 XEN Page 4 40 ...
Page 385: ...ABB Network Partner AB Apparatus control Version 1 0 00 1MRK 580 150 XEN Page 6 100 ...
Page 495: ...ABB Network Partner AB Interlocking Version 1 0 00 1MRK 580 151 XEN Page 6 210 ...
Page 515: ...ABB Network Partner AB Event function Version 1 0 00 1MRK 580 140 XEN Page 6 230 ...
Page 519: ...ABB Network Partner AB Page IV ...
Page 561: ...ABB Network Partner AB Time synchronisation Version 1 0 00 1MRK 580 135 XEN Page 7 42 ...
Page 569: ...ABB Network Partner AB Internal events Version 1 0 00 1MRK 580 134 XEN Page 7 50 ...
Page 599: ...ABB Network Partner AB Index Version 1 0 01 1MRK 580 175 XEN Page 8 6 ...
Page 634: ......
Page 635: ......
Page 636: ......
Page 637: ......
Page 638: ......
Page 639: ......
Page 640: ......
Page 641: ......
Page 642: ......
Page 643: ......