Program features 61
Adaptive programming
Conventionally, you can control the operation of the drive by parameters. However,
the standard parameters have a fixed set of choices or a setting range. To further
customize the operation of the drive, an adaptive program can be constructed out of a
set of function blocks.
The Drive composer pro PC tool (version 1.11 or later, available separately) has an
Adaptive programming feature with a graphical user interface for building the custom
program. The function blocks include the usual arithmetic and logical functions, as
well as e.g., selection, comparison and timer blocks.
The physical inputs, drive status information, actual values, constants and
parameters can be used as the input for the program. The output of the program can
be used e.g., as a start signal, external event or reference, or connected to the drive
outputs. See the table below for a listing of the available inputs and outputs.
If you connect the output of the adaptive program to a selection parameter that is a
pointer parameter, the selection parameter will be write-protected.
Example
:
If parameter
31.01 External event 1 source
is connected to an adaptive
programming block output, the parameter value is shown as
Adaptive program
on
a control panel or PC-tool. The parameter is write-protected (= the selection
cannot be changed).
The status of the adaptive program is shown by parameter
07.30
Adaptive program
status
.
For more information, see the
Adaptive programming application guide
(3AXD50000028574 [English]).
Inputs available to the adaptive program
Input
Source
I/O
DI1
10.02
DI delayed status
, bit 0
DI2
10.02
DI delayed status
, bit 1
DI3
10.02
DI delayed status
, bit 2
1)
DI4
10.02
DI delayed status
, bit 3
1)
AI1
12.11
AI1 actual value
1)
AI2
12.21
AI2 actual value
1)
DIO1
11.02
DIO delayed status
, bit 0
1)
DIO2
11.02
DIO delayed status
, bit 1
1)
Actual signals
Motor speed
01.01
Motor speed used
Output frequency
01.06
Output frequency
Motor current
01.07
Motor current
Motor torque
01.10
Motor torque
Motor shaft power
01.17
Motor shaft power
Status
Enabled
06.16
Drive status word 1
, bit 0